Special Parameters in
Easy Setting GUI View
Fast Curve y Phase
Disable Directional
Fast Curve y Ground
Disable Directional
Fast Curve y Phase
Directional
Fast Curve y Ground
Directional
Minimum Trip Delayed
Curve y Phase
Minimum Trip Delayed
Curve y Ground
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
YES
NO
YES
NO
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
1 A
0.10 .. 4.00 A; ∞
5 A
0.50 .. 20.00 A; ∞
1 A
0.05 .. 4.00 A; ∞
5 A
0.25 .. 20.00 A; ∞
2.29 Recloser Setting Summary
Default Setting Description
YES
This setting will determine
if the Fast curve y
phase would disable
direction judgement.
YES
This setting will determine
if Fast curve y
ground would disable
direction judgement.
Forward
This setting will determine
that the Fast curve y
phase would pickup in
forward, reverse direction
or no-direction required.
Forward
This setting will determine
that the Fast curve y
ground would pickup in
forward, reverse direction
or no-direction required.
1.00 A
Set the minimum trip
values for the Delayed
5.00 A
curve y phase.
0.20 A
Set the minimum trip
values for the Delayed
1.00 A
curve y ground.