relationship of make-break operations and tripping current. The two vertices of this characteristic in a double
logarithmic scale are decisive for the setting of addresses 260 to 263:
Point P1 is determined by the number of permitted make-break operations (parameter 261 OP.CYCLES AT
Ir) for rated operational current Ιr (parameter 260 Ir-52)
Point P2 is determined by the maximum number of make-break operations (parameter 263 OP.CYCLES Isc)
for rated fault tripping current Ιsc (parameter 262 Isc-52).
For the procedure to operate correctly, the time response of the circuit breaker must be specified in parame-
ters 266T 52 BREAKTIME and 267T 52 OPENING.
2
t-Procedure
Ι
The Ι
t-procedure is activated via configuration parameter 172 52 B.WEAR MONIT. The square fault current
2
integrals are referred to the squared device nominal current. For purposes of determining the arc time, the
device must be informed of the CB tripping time T 52 BREAKTIME as well as the CB opening time T 52
OPENING of the circuit breaker. For recognition of the last zero crossing (arc deletion) of the currents after
tripping, the "Current-zero" Criterion is required.
2.26.2.4

Information List

No.
Information
-
#of TRIPs=
409
>BLOCK Op Count
1020
Op.Hours=
1021
Σ Ia =
1022
Σ Ib =
1023
Σ Ic =
2896
79 #Close1./3p=
2898
79 #Close2./3p=
6081
79 #Close1./p1=
6082
79 #Close2./p1=
6083
79 #Close1./p2=
6084
79 #Close2./p2=
6085
79 #Close1./p3=
6086
79 #Close2./p3=
16001
ΣI^x A=
16002
ΣI^x B=
16003
ΣI^x C=
16006
Resid.Endu. A=
16007
Resid.Endu. B=
16008
Resid.Endu. C=
16011
mechan.TRIP A=
16012
mechan.TRIP B=
16013
mechan.TRIP C=
16014
ΣI^2t A=
16015
ΣI^2t B=
16016
ΣI^2t C=
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Type of
Comments
Informa-
tion
PMV
Number of TRIPs=
SP
>BLOCK Op Counter
VI
Counter of operating hours
VI
Accumulation of interrupted current Ph A
VI
Accumulation of interrupted current Ph B
VI
Accumulation of interrupted current Ph C
VI
No. of 1st AR-cycle CLOSE commands,3pole
VI
No. of higher AR-cycle CLOSE commands,3p
VI
No. of 1st AR-cycle CLOSE commands Ph 1
VI
No. of higher AR-cycle CLOSE cmd. Ph 1
VI
No. of 1st AR-cycle CLOSE commands Ph 2
VI
No. of higher AR-cycle CLOSE cmd. Ph 2
VI
No. of 1st AR-cycle CLOSE commands Ph 3
VI
No. of higher AR-cycle CLOSE cmd. Ph 3
VI
Sum Current Exponentiation Ph A to Ir^x
VI
Sum Current Exponentiation Ph B to Ir^x
VI
Sum Current Exponentiation Ph C to Ir^x
VI
Residual Endurance Phase A
VI
Residual Endurance Phase B
VI
Residual Endurance Phase C
VI
Number of mechanical Trips Phase A
VI
Number of mechanical Trips Phase B
VI
Number of mechanical Trips Phase C
VI
Sum Squared Current Integral Phase A
VI
Sum Squared Current Integral Phase B
VI
Sum Squared Current Integral Phase C