Siemens 7SC80 Manual page 640

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
1361
51N-3 Rec. Cur.
1362
51N-4 ANSI Cur.
1363
51N-4 Rec. Cur.
1370
50N HLT PICKUP
1371
50N HLT DELAY
1372A 50N HLT meas.
1385
51N-1 Min O. T
1386
51N-2 Min O. T
640
Function
C
Setting Options
50/51 Overcur.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
50/51 Overcur.
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
50/51 Overcur.
0.05 .. 30.00 A; ∞
50/51 Overcur.
0.00 .. 7200.00 sec;
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
0.00 .. 30.00 sec
50/51 Overcur.
0.00 .. 30.00 sec
Default Setting
Comments
NO
51N-3 Recloser Curve
NO
51N-4 ANSI Curve
NO
51N-4 Recloser Curve
0.50 A
50N Hotline Tag Pickup
0.10 sec
50N Hotline Tag Time
Delay
Fundamental
50N Hotline Tag measure-
ment of
0.01 sec
Min Operating Time
51N-1
0.01 sec
Min Operating Time
51N-2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents