Fault Locator - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Technical Data

4.18 Fault Locator

4.18
Fault Locator
Output of the fault distance
Trigger
Reactance per unit length setting (secon-
dary)
For the remaining parameters refer to the Power System Data 2.
When configuring mixed lines, the reactance per unit length value must be set for each line section (A1 to
A3).
Measurement tolerance as per VDE 0435, Part 303 for
sinusoidal measured quantities
1)
Homogeneous lines or correctly configured line sections are assumed when the fault distance is given in km,
miles or %!
556
in Ω primary and secondary
in km or miles of line length
or in % of the line length
with tripping,
with dropout or
from an external source via binary input
for Ι
= 1 A 0.0050 to 9.5000 Ω/km
Nom
0.0050 to 15.0000 Ω/Meile
for Ι
= 5 A 0.0010 to 1.9000 Ω/km
Nom
0.0010 to 3.0000 Ω/Meile
2.5 % fault location (without intermediate infeed)
30° ≤ φ
≤ 90° and V
K
1)
Increments
0.0001
Increments
0.0001
Increments
0.0001
Increments
0.0001
/V
≥ 0.1 and Ι
K
Nom
K
Nom
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
≥ 1.0