Siemens 7SC80 Manual page 99

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
1269
51-4 Drop-out
1270
50 HLT PICKUP
1271
50 HLT DELAY
1272A
50 HLT meas.
1273
51-4 IEC Curve
1274A
51-4V Influence
1275A
51-4V V<
1276
51-4 Time adder
1277
51-1 ANSI Curve
1278
51-1 Rec. Curve
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
Instantaneous
Disk Emulation
1A
0.10 .. 30.00 A; ∞
5A
0.50 .. 150.00 A; ∞
0.00 .. 7200.00 sec; ∞
Fundamental
True RMS
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
NO
Volt. controll.
Volt. restraint
10.0 .. 125.0 V
0.00 .. 30.00 sec
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Comments
Disk Emulation
Drop-out characteristic
4.00 A
50 Hotline Tag Pickup
20.00 A
0.00 sec
50 Hotline Tag Time Delay
Fundamental
50 Hotline Tag measure-
ment of
Normal Inverse
51-4 IEC Curve
NO
51-4V Voltage Influence
50.0 V
51-4V V<Threshold for
Release Ip
0.00 sec
Constant time adder 51-4
NO
51-1 ANSI Curve
NO
51-1 Recloser Curve
Functions
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents