Functions
2.4 Dynamic Cold Load Pickup
Addr.
Parameter
2013
67c-TOC Recl.
2014
67c-TOC-1 PU
2015
67c-TOC-1 TD
2016
67c-TOC-1 D.o.
2017
67c-TOC-1 IEC
2018
67c-TOC-1 T ad.
2019
67c-TOC-1 ANSI
162
C
Setting Options
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1A
0.10 .. 4.00 A; ∞
5A
0.50 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
Curve A (101)
Recloser Curve
1.00 A
67c-TOC-1 Pickup
5.00 A
0.50 sec
67c-TOC-1 Time Dial
Disk Emulation
Drop-out Characteristic
Normal Inverse
67c-TOC-1 IEC Curve
0.00 sec
Constant time adder 67c-
TOC-1
NO
67c-TOC-1 ANSI Curve
SIPROTEC Compact, 7SC80, Manual