Functions
2.12 Monitoring Functions
[7sc80-ct-supervision-131106, 1, en_US]
Figure 2-75
The voltage transformer monitoring and current transformer monitoring functions can only be used if the
measuring voltages Van, Vbn, Vcn or Vab, Vbc, VGnd are present at the device and parameter 213 VT
Connect. 3ph is set accordingly. If you have selected the wiring Vab, Vbc was selected, the monitoring
functions described above cannot be used.
2.12.1.9

Settings

The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
2201
INRUSH REST.
2202
2nd HARMONIC
2204
CROSS BLK TIMER
2205
I Max
2206
INRUSH DET. BY
5310
BLOCK PROT.
5501
46BC
5502
T 46BC
5503
Curr. Factor BC
5504
Volt. Factor BC
5505
CT Location
5506
VT Location
5510
60VTS
240
Current transformer monitoring
C
Setting Options
OFF
ON
10 .. 50 %
0.00 .. 180.00 sec
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Phase
Cross
Sum
NO
YES
OFF
ON
0.00 .. 100.00 sec
0.00 .. 1.00
0.00 .. 1.00
Direction 1
Direction 2
Direction 1
Direction 2
OFF
ON with NPS
Default Setting
Comments
OFF
Inrush Restraint
15 %
2nd. harmonic in % of
fundamental
0.00 sec
Cross Block Time
7.50 A
Maximum Current for
Inrush Restraint
37.50 A
Phase
Inrush detected by
YES
Block protection by 60VTS
OFF
46 Broken Conductor
2.00 sec
46BC Delay Time
0.10
Current Factor for Broken
Conductor
0.10
Voltage Factor for Broken
Conductor
Direction 1
Measurement location of
CT
Direction 1
Measurement location of
VT
OFF
60VTS Voltage Transformer
Supervision
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017