Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
Addr.
Parameter
3102
CT Err. I1
3103
CT Err. F1
3104
CT Err. I2
3104
CT Err. I2
3105
CT Err. F2
3106
VPH MIN
3107
VPH MAX
3109
64-1 VGND
3110
64-1 VGND
3111
T-DELAY Pickup
3112
64-1 DELAY
3113
50Ns-2 PICKUP
3113
50Ns-2 PICKUP
3114
50Ns-2 DELAY
3115
67Ns-2 DIRECT
3117
50Ns-1 PICKUP
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3119
51Ns PICKUP
3120
51NsTIME DIAL
3121A
50Ns T DROP-OUT
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
266
C
Setting Options
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
0.0 .. 5.0 °
1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
0.0 .. 5.0 °
10 .. 100 V
10 .. 100 V
1.8 .. 200.0 V; ∞
5.0 .. 225.0 V; ∞
0.04 .. 320.00 sec; ∞
0.10 .. 40000.00 sec; ∞
1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
0.00 .. 320.00 sec; ∞
Forward
Reverse
Non-Directional
1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
0.00 .. 320.00 sec; ∞
1A
0.001 .. 1.400 A
5A
0.005 .. 7.000 A
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.10 .. 4.00 sec; ∞
0.00 .. 60.00 sec
Forward
Reverse
Non-Directional
1A
0.001 .. 1.200 A
5A
0.005 .. 6.000 A
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
-45.0 .. 45.0 °
COS φ
SIN φ
Default Setting
Comments
1.00 A
Current I1 for CT Angle
Error
5.00 A
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle
Error
5.000 A
10.00 A
Current I2 for CT Angle
Error
50.00 A
0.0 °
CT Angle Error at I2
40 V
L-Gnd Voltage of Faulted
Phase Vph Min
75 V
L-Gnd Voltage of Unfaulted
Phase Vph Max
40.0 V
64-1 Ground Displacement
Voltage
70.0 V
64-1 Ground Displacement
Voltage
1.00 sec
Time-DELAY Pickup
10.00 sec
64-1 Time Delay
0.300 A
50Ns-2 Pickup
1.500 A
10.00 A
50Ns-2 Pickup
50.00 A
1.00 sec
50Ns-2 Time Delay
Forward
67Ns-2 Direction
0.100 A
50Ns-1 Pickup
0.500 A
2.00 A
50Ns-1 Pickup
10.00 A
2.00 sec
50Ns-1 Time delay
0.100 A
51Ns Pickup
0.500 A
1.00 A
51Ns Pickup
5.00 A
1.00 sec
51Ns Time Dial
0.00 sec
50Ns Drop-Out Time Delay
Forward
67Ns-1 Direction
0.010 A
Release directional element
0.050 A
0.50 A
Release directional element
2.50 A
0.0 °
Correction Angle for Dir.
Determination
COS φ
Measurement method for
Direction