Siemens 7SC80 Manual page 421

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Special Parameters in
Easy Setting GUI View
CLP Curve x Phase
CLP Curve x Phase
Time Dial
CLP Curve x Phase
Reset
CLP Curve x Phase
Time Adder
CLP Curve x Phase Min
Operating Time
Minimum Trip CLP
Curve x Ground
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
IEC Curve - Normal Inverse
IEC Curve - Very Inverse
IEC Curve - Extremely Inverse
IEC Curve - Long Inverse
ANSI Curve - Inverse
ANSI Curve - Short Inverse
ANSI Curve - Long Inverse
ANSI Curve - Moderately Inverse
ANSI Curve - Very Inverse
ANSI Curve - Extremely Inverse
ANSI Curve - Definite Inverse
Recloser Curve - Curve A (101)
Recloser Curve - Curve B (117)
Recloser Curve - Curve C (133)
Recloser Curve - Curve D (116)
Recloser Curve - Curve E (132)
Recloser Curve - Curve K (162)
Recloser Curve - Curve N (104)
Recloser Curve - Curve R (105)
Recloser Curve - Curve W (138)
Recloser Curve - Curve 2 (135)
Recloser Curve - Curve 3 (140)
Recloser Curve - Curve 8 (113)
Recloser Curve - Curve 8* (111)
Recloser Curve - Curve 9 (131)
Recloser Curve - Curve 11 (141)
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
0.00 .. 30.00 sec
0.00 .. 30.00 sec
1 A
0.05 .. 4.00 A; ∞
5 A
0.25 .. 20.00 A; ∞
2.29 Recloser Setting Summary
Default Setting Description
IEC Curve -
Set the trip curve type for
Normal Inverse
the CLP curve x
phase.
0.50 sec
Set the time dial for the
CLP curve x phase.
Disk Emulation
Set the reset characteristic
for the CLP curve x
phase.
0.00 sec
Set the time adder for the
CLP curve x phase.
0.01 sec
Set the minimum oper-
ating time for CLP curve
x phase.
0.20 A
Set the minimum trip
values for the CLP curve
1.00 A
x ground.
Functions
421