Functions, Settings, Information
F.2 Settings
Addr. Parameter
1344A 51N-3 measure.
1345
51N-3 PICKUP
1346
51N-3 T DIAL
1347
51N-3 Drop-out
1348
51N-3 IEC Cur.
1349
51N-3 T adder
1350A 51N-4 measure.
1351
51N-4 PICKUP
1352
51N-4 T DIAL
1353
51N-4 Drop-out
1354
51N-4 IEC Cur.
1355
51N-4 T adder
1356
51N-1 ANSI Cur.
638
Function
C
Setting Options
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur. 1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
50/51 Overcur.
0.01 .. 20.00 sec; ∞ 0.20 sec
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
0.00 .. 30.00 sec
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur. 1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
50/51 Overcur.
0.01 .. 20.00 sec; ∞ 0.20 sec
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
0.00 .. 30.00 sec
50/51 Overcur.
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
Fundamental
51N-3 measurement of
0.20 A
51N-3 Pickup
1.00 A
51N-3 Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
51N-3 IEC Curve
0.00 sec
Constant time adder
51N-3
Fundamental
51N-4 measurement of
0.20 A
51N-4 Pickup
1.00 A
51N-4 Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
51N-4 IEC Curve
0.00 sec
Constant time adder
51N-4
NO
51N-1 ANSI Curve
SIPROTEC Compact, 7SC80, Manual