Settings - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

exceeding of the pickup threshold, for example, with power protection or when a function is not used as a
protection, but as a monitoring function.
When setting the power threshold values, it is important to take into consideration that a minimum current of
0.03 Ι
is required for power calculation. The power calculation is blocked for lower currents.
N
The dropout of pickup can be delayed via parameter T DROPOUT DELAY. This setting is also set to zero by
default (standard setting). A setting deviating from zero may be required if the device is utilized together with
electro-magnetic devices with considerably longer dropout ratios than the digital protection device (see
Chapter
General, Page
set it to a shorter time than the OFF-command time delay in order to avoid both times to "race".
The dropout ratio of the function can be selected in parameter DROPOUT RATIO. The standard dropout ratio
of protection functions is 0.95 (default setting). If the function is used as power protection, a dropout ratio of
at least 0.9 should be set. The same applies to the utilization of the symmetrical components of current and
voltage. If the dropout ratio is decreased, it would be sensible to test the pickup of the function regarding
possible "chatter".
The dropout difference of the frequency elements is set under parameter DO differential. Usually, the
default setting of 0.02 Hz can be retained. A higher dropout difference should be set in weak systems with
larger, short-term frequency fluctuations to avoid chattering of the message.
A fixed dropout difference of 0.1 Hz/s is used for the frequency change (df/dt) measurand. The same applies to
the voltage change (dV/dt) measurand. The permanent dropout difference here is 3 V/s.
Parameter BLK.by Vol.Loss determines whether a function whose measured variable is based on a voltage
measurement (measured quantities voltage, P forward, P reverse, Q forward, Q reverse and power factor),
should be blocked in case of a measured voltage failure (set to YES) or not (set to NO).
Renaming Messages, Checking Configurations
After parameterization of a flexible function, the following steps should be noted:
Open matrix in DIGSI
Rename the neutral message texts in accordance with the application.
Check configurations on contacts and in operation and fault buffer, or set them according to the require-
ments.
Further Information
The following instruction should be noted:
As the power factor does not differentiate between capacitive and inductive, the sign of the reactive
power may be used with CFC-help as an additional criterion.
2.19.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
87for more information). When utilizing the dropout time delay, it is recommended to
C
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
2.19 Flexible Protection Functions
Default Setting
Comments
OFF
Flexible Function
3-phase
Mode of Operation
Functions
333

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents