Addr. Parameter
5141
27-2 PhC Pickup
5142
27-1 PhA Delay
5143
27-1 PhB Delay
5144
27-1 PhC Delay
5145
27-2 PhA Delay
5146
27-2 PhB Delay
5147
27-2 PhC Delay
5310
BLOCK PROT.
5401
FCT 81 O/U
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
5410
81-3 PICKUP
5411
81-3 DELAY
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
5415A DO differential
5421
FCT 81-1 O/U
5422
FCT 81-2 O/U
5423
FCT 81-3 O/U
5424
FCT 81-4 O/U
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
Meas-
NO
urem.Superv
YES
81 O/U Freq.
OFF
ON
81 O/U Freq.
10 .. 150 V
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
40.00 .. 60.00 Hz
81 O/U Freq.
50.00 .. 70.00 Hz
81 O/U Freq.
0.00 .. 100.00 sec;
81 O/U Freq.
0.02 .. 1.00 Hz
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
81 O/U Freq.
OFF
ON f>
ON f<
Functions, Settings, Information
Default Setting
Comments
40 V
27-2 Phase C Pickup
1.50 sec
27-1 Phase A Time Delay
1.50 sec
27-1 Phase B Time Delay
1.50 sec
27-1 Phase C Time Delay
0.50 sec
27-2 Phase A Time Delay
0.50 sec
27-2 Phase B Time Delay
0.50 sec
27-2 Phase C Time Delay
YES
Block protection by 60VTS
OFF
81 Over/Under Frequency
Protection
65 V
Minimum required
voltage for operation
49.50 Hz
81-1 Pickup
59.50 Hz
81-1 Pickup
60.00 sec
81-1 Time Delay
49.00 Hz
81-2 Pickup
59.00 Hz
81-2 Pickup
30.00 sec
81-2 Time Delay
47.50 Hz
81-3 Pickup
57.50 Hz
81-3 Pickup
3.00 sec
81-3 Time delay
51.00 Hz
81-4 Pickup
61.00 Hz
81-4 Pickup
30.00 sec
81-4 Time delay
0.02 Hz
Dropout differential
OFF
81-1 Over/Under
Frequency Protection
OFF
81-2 Over/Under
Frequency Protection
OFF
81-3 Over/Under
Frequency Protection
OFF
81-4 Over/Under
Frequency Protection
F.2 Settings