Functions, Settings, Information
F.2 Settings
Addr. Parameter
6015
S2: Line angle
6016
S2: Line length
6017
S2: Line length
6021
S3: RE/RL
6022
S3: XE/XL
6023
S3: x'
6024
S3: x'
6025
S3: Line angle
6026
S3: Line length
6027
S3: Line length
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A Direct CO
6111A TSUP VOLTAGE
6112
T-SYN. DURATION
6113A 25 Synchron
672
Function
C
Setting Options
P.System Data
10 .. 89 °
2
P.System Data
0.1 .. 650.0 Miles
2
P.System Data
0.1 .. 1000.0 km
2
P.System Data
-0.33 .. 7.00
2
P.System Data
-0.33 .. 7.00
2
P.System Data
1A
0.0050 ..
2
15.0000 Ω/mi
5A
0.0010 ..
3.0000 Ω/mi
P.System Data
1A
0.0050 ..
2
9.5000 Ω/km
5A
0.0010 ..
1.9000 Ω/km
P.System Data
10 .. 89 °
2
P.System Data
0.1 .. 650.0 Miles
2
P.System Data
0.1 .. 1000.0 km
2
SYNC function
ON
1
OFF
SYNC function
(Setting options
1
depend on configu-
ration)
SYNC function
20 .. 125 V
1
SYNC function
20 .. 140 V
1
SYNC function
1 .. 60 V
1
SYNC function
20 .. 140 V
1
SYNC function
YES
1
NO
SYNC function
YES
1
NO
SYNC function
YES
1
NO
SYNC function
YES
1
NO
SYNC function
0.00 .. 60.00 sec
1
SYNC function
0.01 .. 1200.00 sec;
1
SYNC function
YES
1
NO
Default Setting
Comments
85 °
S2: Line angle
62.1 Miles
S2: Line length in miles
100.0 km
S2: Line length in kilo-
meter
1.00
S3: Zero seq. compen-
sating factor RE/RL
1.00
S3: Zero seq. compen-
sating factor XE/XL
0.2420 Ω/mi
S3: feeder reactance per
mile: x'
0.0484 Ω/mi
0.1500 Ω/km
S3: feeder reactance per
km: x'
0.0300 Ω/km
85 °
S3: Line angle
62.1 Miles
S3: Line length in miles
100.0 km
S3: Line length in kilo-
meter
OFF
Synchronizing Function
none
Synchronizable circuit
breaker
90 V
Minimum voltage limit:
Vmin
110 V
Maximum voltage limit:
Vmax
5 V
Threshold V1, V2 without
voltage
80 V
Threshold V1, V2 with
voltage
NO
ON-Command at V1< and
V2>
NO
ON-Command at V1> and
V2<
NO
ON-Command at V1< and
V2<
NO
Direct ON-Command
0.10 sec
Supervision time of
V1>;V2> or V1<;V2<
30.00 sec
Maximum duration of
Synchronization
YES
Switching at synchronous
condition
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement