Settings - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.8 27/59 Under/Over Voltage for Vx
Select the time settings in such a way that admissible brief voltage peaks generated during switching opera-
tions do not generate a tripping and that stationary overvoltages can be tripped in time.
The dropout thresholds are set at the following addresses:
59-1 Vx DOut R. Address 395
59-2 Vx DOut R. Address 396
The minimum hysteresis is 0.6 V.
Undervoltage Protection
Undervoltage protection includes two elements.
You can set the pickup thresholds at the following addresses:
27-1 Vx Pickup
27-2 Vx Pickup
The times for tripping delay are set at the following addresses:
27-1 Vx Delay
27-2 Vx Delay
The time settings should be selected in such a way that tripping occurs in case of voltage dips that lead to
unstable operating conditions. On the other hand, time delays should be long enough to avoid tripping due to
momentary voltage dips.
The dropout thresholds are set at the following addresses:
27-1 Vx DOut R. Address 385
27-2 Vx DOut R. Address 386
The minimum hysteresis is 0.6 V.

Settings

2.8.3
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
380
27 Vx
381
27-1 Vx Pickup
382
27-2 Vx Pickup
383
27-1 Vx Delay
384
27-2 Vx Delay
385A
27-1 Vx DOut R.
386A
27-2 Vx DOut R.
390
59 Vx
391
59-1 Vx Pickup
392
59-2 Vx Pickup
393
59-1 Vx Delay
394
59-2 Vx Delay
395A
59-1 Vx DOut R.
396A
59-2 Vx DOut R.
206
Address 381
Address 382
Address 383
Address 384
Setting Options
OFF
ON
Alarm Only
10 .. 120 V
10 .. 120 V
0.00 .. 60.00 sec; ∞
0.00 .. 60.00 sec; ∞
1.01 .. 3.00
1.01 .. 3.00
OFF
ON
Alarm Only
20 .. 150 V
20 .. 150 V
0.00 .. 60.00 sec; ∞
0.00 .. 60.00 sec; ∞
0.90 .. 0.99
0.90 .. 0.99
Default Setting
Comments
OFF
27 Undervoltage prot. for Vx
35 V
Undervoltage Vx< pickup
30 V
Undervoltage Vx<< pickup
0.50 sec
Undervoltage Vx< delay time
0.50 sec
Undervoltage Vx<< delay time
1.20
27-1 Vx Dropout Ratio
1.20
27-2 Vx Dropout Ratio
OFF
59 Overvoltage prot. for Vx
140 V
Overvoltage Vx> pickup
145 V
Overvoltage Vx>> pickup
0.50 sec
Overvoltage Vx> delay time
0.50 sec
Overvoltage Vx>> delay time
0.95
59-1 Vx Dropout Ratio
0.95
59-2 Vx Dropout Ratio
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents