Siemens 7SC80 Manual page 38

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.1 General
Addr.
Parameter
172
52 B.WEAR MONIT
180
Fault Locator
181
L-sections FL
182
74 Trip Ct Supv
350
Bat. Monitor
368
AssignMeasInput
369
VT Con Type
370
27/59 Vx
371
Capacitor Ctrl.
372
Tap Changer
374
Triple Single
375
Capacitor Test
376
Sectionalizer
377
VT Con Type S2
38
Setting Options
Disabled
Ix-Method
2P-Method
I2t-Method
Disabled
Enabled
1 Section
2 Sections
3 Sections
Disabled
2 Binary Inputs
1 Binary Input
Disabled
Enabled
Ia, Ib, Ic, Vx
INs,Ib,Ic,Vx=Ia
Ia, INs, Ic, Vx
CONVENTIONAL
LoPo/LPS
Cap. Volt.Meas.
Enabled
Disabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
With prot.
Without prot.
CONVENTIONAL
LoPo/LPS
Cap. Volt.Meas.
Default Setting
Comments
Disabled
52 Breaker Wear Monitoring
Disabled
Fault Locator
1 Section
Line sections for fault locator
Disabled
74TC Trip Circuit Supervision
Disabled
Battery voltage Monitor
Ia, Ib, Ic, Vx
Assignment measurement inputs
CONVENTIONAL
Voltage connection type
Disabled
27/59 Over/under volt. Prot. for Vx
Disabled
Capacitor Control
Disabled
Tap Changer
Disabled
Triple Single Mode
Disabled
Recloser capacitor Test
Disabled
Sectionalizer Function
CONVENTIONAL
Voltage connection type Side2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links: