Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
Addr.
Parameter
351
Bat. Monitor
352
V bat. crit.
353
V bat. nom.
354
BatTestInterval
355
BatVoltDropLoad
356
T load active
357
BatVoltDrpLdTst
358
BatTestDelay
610
FltDisp.LED/LCD
611
Spont. FltDisp.
618
Direct Control
620
Remote FwUpdate
640
Start image DD
700
GOOSE-Stop
702A
Fast IO-Box
710
EvLog Fill Lev1
711
EvLog Fill Lev2
46
CFC – service interlocking control via function key
Setting Options
ON
OFF
22.0 .. 48.0 V
22.0 .. 48.0 V
12 .. 672 hour
0.1 .. 5.0 V
0.1 .. 60.0 sec
0.1 .. 5.0 V
1 .. 60 min
Target on PU
Target on TRIP
YES
NO
NO
YES
Disabled
Enabled
image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
image 9
YES
NO
OFF
ON
10 .. 100 %
10 .. 100 %
Default Setting
Comments
ON
Battery voltage Monitor
23.0 V
Battery critical voltage level
24.0 V
Nominal battery voltage level
48 hour
Battery test time interval
0.5 V
Battery voltage drop caused by
test load
5.0 sec
Test load active time
0.5 V
Battery voltage drop after load
test
30 min
Start battery test delay
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of flt.annun-
ciations
NO
Direct control of open/close
buttons
Disabled
Remote firmware update
image 1
Start image Default Display
NO
GOOSE-Stop
OFF
Fast GOOSE transmission
70 %
Threshold Fill level 1 Event Log
90 %
Threshold Fill level 2 Event Log
SIPROTEC Compact, 7SC80, Manual