2 – 90
Warning
The maximum cable length between the SM 1xx and the inverter is 1 m.
Select the cross section of the grounding conductor (yellow/green) at the
voltage protection module so that the cross section of the grounding
conductor is not less than half the cross section of the leads to the SM 1xx
(e. g. leads = 40 mm
However, a cross section of at least 10 mm
conductor.
Warning
Due to the high power, the SM 130 features a temperature switch. The
switch must be evaluated in the EMERGENCY STOP chain. The switch
opens at temperatures above 60 °C. This makes it possible to prevent a
subsequent switch-on temporarily.
Warning
With the SM 130, the three motor phases are connected to three screws
located in the housing of the SM 130. Use only insulated terminals for the
connection. The tightening torque for the screws is approximately 9 Nm.
Specifications
Switching voltage
Maximum phase
current
Maximum braking
time at maximum
phase current
Minimum duration
between braking
procedures
Degree of
protection
Weight
ID
Connection
HEIDENHAIN Technical Manual for Inverter Systems and Motors
2
, then the grounding conductor = 20 mm
SM 110
830 V
3 x 63 A
IP 20
Approx. 2.1 kg
368 453-01
Page 4–34
2
).
2
is required for the grounding
SM 130
830 V
3 x 300 A
10 s
5 min
IP 20
Approx. 6.3 kg
540 739-01
Page 4–34