B.3 Parameter Table
H1-
Function
Setting
1B
Program lockout
20 to 2F
External fault
30
PID integral reset
31
PID integral hold
34
PID soft starter cancel
35
PID input level selection
40
Forward run command (2-wire sequence)
41
Reverse run command (2-wire sequence)
42
Run command (2-wire sequence 2)
43
FWD/REV command (2-wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
50
Disturb Function Cancel
51
Synchronous Accel/Decel
53
Energy Saving On/Off
390
H1 Multi-Function Digital Input Selections
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
All Modes
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
All Modes
Closed: Resets the PID control integral value.
All Modes
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
All Modes
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
All Modes
Closed: Inverts the PID input signal
All Modes
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
All Modes
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run command. Cannot be set together with settings 40 or
41.
All Modes
Closed: Adds d7-01 to the frequency reference.
All Modes
Closed: Adds d7-02 to the frequency reference.
All Modes
Closed: Adds d7-03 to the frequency reference.
All Modes
Open: Disturb function output is active.
Closed: Cancels the Disturb function.
All Modes
Closed: Assigns the same accel/decel times to all motors in the line so that they reach the desired frequency at the
same time.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Enables the Energy Saving function.