5.7 H: Terminal Functions
4.
Use the ASR gain and integral time parameters described in
page 146
for adjusting the responsiveness.
Note: 1. C5 parameters will appear when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for simple PG feedback in
V/f Control (H6-01 = 3).
2. If running two motors from the same drive, note that the V/f Control with simple PG feedback can be used for motor 1 only.
n
H6-02: Pulse Train Input Scaling
This parameter sets the pulse signal frequency that is equal to 100% of the input value selected in parameter H6-01.
No.
H6-02
n
H6-03: Pulse Train Input Gain
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
No.
H6-03
n
H6-04: Pulse Train Input Bias
Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
No.
H6-04
n
H6-05: Pulse Train Input Filter Time
Sets the pulse train input filter time constant in seconds.
No.
H6-05
n
H6-06: Pulse Train Monitor Selection
Selects the monitor to output as a pulse train signal via terminal MP. Indicate which monitor to output entering the three
digits in U -
.
Refer to U: Monitors on page 414
H6-06 appear in the table below.
No.
H6-06
<1> Set this value as 000 when using the terminal in the pass-through mode.
n
H6-07: Pulse Train Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the specified monitor item is at 100%. Set H6-
06 to 102 and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
No.
H6-07
n
H6-08: Pulse Train Input Minimum Frequency
Sets the minimum output frequency that can be detected by the pulse train input. Decreasing this setting reduces the time
the drive needs to react to changes in the input signal.
• If the pulse input frequency falls below this level, the pulse input value will be 0.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
H6-08
210
Name
Pulse Train Input Scaling
Name
Pulse Train Input Gain
Name
Pulse Train Input Bias
Name
Pulse Train Input Filter Time
for a complete list of monitors. Monitors that can be selected by
Name
Pulse Train Monitor Selection
Name
Pulse Train Monitor Scaling
Name
Pulse Train Input Minimum Frequency
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
C5: Automatic Speed Regulator (ASR) on
Setting Range
100 to 32000 Hz
Setting Range
0.0 to 1000.0%
Setting Range
-100.0 to 100.0%
Setting Range
0.00 to 2.00 s
Setting Range
000
, 031
, 101, 102, 105, 116,
<1>
<1>
501, 502
Setting Range
0 to 32000 Hz
Setting Range
0.1 to 1000.0 Hz
Default
1440 Hz
Default
100.0%
Default
0.0%
Default
0.10 s
Default
102
Default
1440 Hz
Default
0.5 Hz

Hide quick links: