YASKAWA T1000A Technical Manual page 389

Table of Contents

Advertisement

H1-
Function
Setting
6
Jog reference selection
7
Accel/decel time selection 1
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
A
Accel/decel ramp hold
B
Drive overheat alarm (oH2)
C
Analog terminal input selection
D
PG encoder disable
E
ASR integral reset
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
16
Motor 2 selection
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
1A
Accel/decel time selection 2
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
H1 Multi-Function Digital Input Selections
All Modes
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference sources.
All Modes
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set in C1-03, C1-04).
All Modes
Closed: No drive output
All Modes
Open: No drive output
All Modes
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the output frequency.
All Modes
Closed: Closes when an oH2 alarm occurs
All Modes
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Open: Speed feedback for V/f Control with PG is enabled.
Closed: Speed feedback disabled.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Open: PI control
Closed: Integral reset
All Modes
Select this setting when using the terminal in a pass-through mode. The terminal does not trigger a drive function
but can be used as digital input for the controller the drive is connected to.
All Modes
The drive accelerates when the Up command terminal closes, and decelerates when the Down command closes.
When both terminals are closed or both are open, the drive holds the frequency reference. The Up and Down
commands must always be used in conjunction with one another.
All Modes
Closed: Runs forward at the Jog frequency d1-17.
All Modes
Closed: Runs reverse at the Jog frequency d1-17.
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Open: Motor 1 (E1-
, E2-
)
Closed: Motor 2 (E3-
, E4-
)
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output
(H2-
= 12).
All Modes
Open: PID control enabled
Closed: PID control disabled
All Modes
Used in conjunction with an input terminal set for "Accel/decel time selection 1" (H1-
drive to switch between accel/decel times 3 and 4.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
B.3 Parameter Table
Page
183
183
183
183
183
183
184
184
184
184
184
184
185
185
185
185
186
185
186
186
186
= 7), and allows the
389
B

Hide quick links: