YASKAWA T1000A Technical Manual page 371

Table of Contents

Advertisement

No.(Addr.)
Name
b5-04
(1A8H)
Integral Limit Setting
b5-05
(1A9H)
Derivative Time (D)
b5-06
(1AAH)
PID Output Limit
b5-07
(1ABH)
PID Offset Adjustment
b5-08
(1ACH)
PID Primary Delay Time Constant
b5-09
PID Output Level Selection
(1ADH)
b5-10
(1AEH)
PID Output Gain Setting
b5-11
PID Output Reverse Selection
(1AFH)
b5-12
PID Feedback Loss Detection
(1B0H)
Selection
b5-13
(1B1H)
PID Feedback Low Detection
Level
b5-14
(1B2H)
PID Feedback Low Detection
Time
b5-15
(1B3H)
PID Sleep Function Start Level
b5-16
(1B4H)
PID Sleep Delay Time
b5-17
(1B5H)
PID Accel/Decel Time
b5-18
PID Setpoint Selection
(1DCH)
b5-19
(1DDH)
PID Setpoint Value
b5-20
PID Setpoint Scaling
(1E2H)
b5-34
(19FH)
PID Output Lower Limit
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
All Modes
Sets the maximum output possible from the integrator as a percentage of the maximum output
frequency.
All Modes
Sets D control derivative time.
All Modes
Sets the maximum output possible from the entire PID controller as a percentage of the
maximum output frequency.
All Modes
Applies an offset to the PID controller output. Set as a percentage of the maximum output
frequency.
All Modes
Sets a low pass filter time constant on the output of the PID controller.
All Modes
0: Normal output (direct acting)
1: Reverse output (reverse acting)
All Modes
Sets the gain applied to the PID output.
All Modes
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
When using setting 1, make sure reverse operation is permitted by parameter b1-04.
All Modes
0: No fault. Digital output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Digital output only. No fault detection when PID control is disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault detection even when PID
is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control is disabled.
All Modes
Sets the PID feedback loss detection level as a percentage of the maximum output frequency.
All Modes
Sets a delay time for PID feedback loss.
All Modes
Sets the frequency level that triggers the sleep function.
All Modes
Sets a delay time before the sleep function is triggered.
All Modes
Sets the acceleration and deceleration time to PID setpoint.
All Modes
0: Disabled
1: Enabled
All Modes
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum output
frequency.
All Modes
0: 0.01 Hz units
1: 0.01% units (100% = max. output frequency)
2: r/min units (set the no. of motor poles)
3: User-set units (use b5-38, b5-39)
All Modes
Sets the minimum output possible from the PID controller as a percentage of the maximum
output frequency.
Description
B.3 Parameter Table
Setting
Page
Default: 100.0%
Min: 0.0%
130
Max: 100.0%
Default: 0.00 s
Min: 0.00 s
130
Max: 10.00 s
Default: 100.0%
Min: 0.0%
131
Max: 100.0%
Default: 0.0%
Min: -100.0%
131
Max: 100.0%
Default: 0.00 s
Min: 0.00 s
131
Max: 10.00 s
Default: 0
Min: 0
131
Max: 1
Default: 1.00
Min: 0.00
131
Max: 25.00
Default: 0
Min: 0
131
Max: 1
Default: 0
Min: 0
132
Max: 5
Default: 0%
Min: 0%
133
Max: 100%
Default: 1.0 s
Min: 0.0 s
133
Max: 25.5 s
Default:
<34>
Min: 0.0 Hz
134
Max: 400.0 Hz
Default: 0.0 s
Min: 0.0 s
134
Max: 25.5 s
Default: 0.0 s
Min: 0.0 s
134
Max: 6000.0 s
Default: 0
Min: 0
134
Max: 1
Default: 0.00%
Min: 0.00%
134
Max: 100.00%
Default: 1
Min: 0
135
Max: 3
Default: 0.00%
Min: -100.0%
135
Max: 100.0%
371