Installing a Braking Resistor Unit: LKEB type
LKEB type braking resistors provide dynamic braking capability with up to 10% ED. They can be directly connected to
the drives B1 and B2 terminals as shown in
utilized in order to switch off the drive in case braking resistor overheat occurs.
As the drives internal braking resistor overload protection cannot protect LKEB resistors, disable this function by setting
L8-01 to 0.
Figure 8.6
n
Installing Other Types of Braking Resistors
When installing braking resistors other than the ERF or LKEB types, make sure that the drive internal braking transistor
will not be overloaded with the required duty cycle and the selected resistance value. Use a resistor that is equipped with
a thermal overload relay contact, and utilize this contact to switch off the drive in case of braking resistor overheat.
n
Braking Resistor Overload Protection
If using a braking resistor option, a sequence such as the one shown in
supply in case the braking resistor overheats.
Figure 8.7
n
Installing a Braking Unit: CDBR Type
To install a CDBR type braking unit, connect the drive's B1 terminal (units CIMR-T 2A0004 to 0138 and CIMR-
T 4A0002 to 0072) or +3 terminal (units CIMR-T 2A0169 to 0415 and CIMR-T 4A0088 to 4A0362) to the positive
terminal on the braking unit. Next wire the negative terminals on the drive and braking unit together. Terminal +2 is not
used.
Connect the braking resistor to the CDBRs terminals +0 and -0.
Wire the thermal overload relay contact of the CDBR and the braking resistor in series, and connect this signal to a drive
digital input. Use this input to trigger a fault in the drive in case a CDBR or braking resistor overload occurs.
Disable dynamic braking transistor protection by setting L8-55 = 0.
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Figure
8.6. The LKEB unit has a thermal overload contact that should be
B1
Drive
B2
Figure 8.6 Connecting a Braking Resistor Unit: LKEB Type
(CIMR-T 2A0004 to 0138, T 4A0002 to 0072)
Circuit Breaker
R
S
T
MC
MB
2MCCB
THRX
OFF
1
2
Braking Resistor Unit
(Close: Overheat)
Figure 8.7 Power Supply Interrupt for Overheat Protection (Example)
Braking Resistor Unit
(LKEB type)
P
1
Thermal Relay
B
2
Figure 8.7
MC
R/L1
S/L2
T/L3
400/200V
ON
MC
SA
MC
THRX
SA
8.5 Installing Peripheral Devices
Trip Contact
should be set up to interrupt the power
Drive
8
343