Setting 1A: During reverse
A digital output set for "During reverse" will close whenever the drive is running the motor in the reverse direction.
Status
Open
Motor is being driven in the forward direction or stopped.
Closed
Motor is being driven in reverse.
Figure 5.64
Setting 1B: During baseblock (N.C.)
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Setting 1C: Motor 2 selection
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1-
= 16).
Refer to Setting 16: Motor 2 selection on page 186
Status
Open
Motor 1 is selected.
Closed
Motor 2 is selected.
Setting 1D: During regeneration
Terminal closes when the motor is driven in the regenerative mode.
Setting 1E: Restart enabled
An output set for "Restart enabled" closes once the drive begins attempting to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has begun attempting to restart. If the drive cannot successfully restart within the number of
attempts permitted by L5-01, then a fault will be triggered and the terminal set to 1E will open.
Restart on page 225
for details on automatic restart.
Setting 1F: Motor overload alarm (oL1)
An output programmed for this function will close when the motor overload level estimated by the oL1 fault detection
exceeds 10% of the oL1 detection level.
Setting 20: Drive overheat pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02.
Overheat Alarm Level on page 229
Setting 2F: Maintenance period
Output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components. Components performance life is displayed as a
percentage on the digital operator screen.
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 5.64 Reverse Direction Output Example Time Chart
Refer to L1-01: Motor Overload Protection Selection on page
for details on drive overheat detection.
Refer to Periodic Maintenance on page
Description
ON
OFF
Description
for details on switching motors.
Description
317.
5.7 H: Terminal Functions
time
Refer to L5: Fault
211.
Refer to L8-02: