Option K82 (Terminal Module For Controlling The "Safe Torque Off" And "Safe Stop1" Functions) - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

A diagram showing a typical connection of the TM150 Terminal Module with different sensors is shown below.
Typical connection of the TM150 Terminal Module with different temperature sensors in 2-wire, 3-wire and 4-wire circuits
9.3
Option K82 (Terminal module for controlling the "Safe Torque Off" and "Safe Stop1"
functions)
This option is available for SINAMICS G150, SINAMICS S120 Cabinet Modules (only for air-cooled units, but not
currently for liquid-cooled units), SINAMICS S150.
The Safe Torque Off (STO) function prevents a motor from starting unexpectedly from standstill. The Safe Stop1
(SS1) function is braking the rotating motor along a deceleration ramp followed by the transition to STO and thus
reliably preventing the motor from restarting. These two safety functions are a standard feature of SINAMICS G150
converter cabinet units, S120 Cabinet Modules and S150 converter cabinet units.
Description of Options
Engineering Information
SINAMICS Engineering Manual – November 2015
497/528
Ó Siemens AG