7.2.4.2

Planning recommendations, special features

Line Modules should be connected as standard on the right of a Line Connection Module. Line Modules can also be
erected to the left of the LCM with frame size KL and LL. However, this rule applies only to Line Modules. Other types
of Cabinet Modules can be connected at any side of a Line Connection Module. It must be noted that option M26
(side panel mounted on the right) cannot be used on an LCM.
Options L42 (LCM for Active Infeed), L43 (LCM for Basic Line Module) and L44 (LCM for Smart Line Module) must
also be taken into account. These serve to assign the LCM to the adjacent Line Modules. They include precharging
circuits and cable connections to the relevant Infeed or Line Module. For this reason, it is advisable to place the LCM
and Line Modules within the same transport unit. In this case, the necessary cable connections will be made in the
factory.
If a grounding switch is also needed, the space it requires means that an LCM in frame size KL or LL must be used.
7.2.4.3

Assignment to the rectifiers / Line Modules

To simplify the configuring process, the correct Line Connection Modules are already assigned to the rectifiers (Line
Modules). The table below shows the possible combinations.
Line Connection Modules
Current
Order No.
1)
[AC]
A
Supply voltage 380 V - 480 V 3AC
6SL3700-0LE32-5AA3
250
380
6SL3700-0LE34-0AA3
600
6SL3700-0LE36-3AA3
6SL3700-0LE38-0AA3
770
1000
6SL3700-0LE41-0AA3
6SL3700-0LE41-3AA3
1250
6SL3700-0LE41-6AA3
1600
2000
6SL3700-0LE42-0AA3
2000
6SL3700-0LE42-0BA3
6SL3700-0LE42-5BA3
2500
6SL3700-0LE43-2BA3
3200
Supply voltage 500 V - 690 V 3AC
6SL3700-0LG32-8AA3
280
380
6SL3700-0LG34-0AA3
600
6SL3700-0LG36-3AA3
6SL3700-0LG38-0AA3
770
1000
6SL3700-0LG41-0AA3
1250
6SL3700-0LG41-3AA3
6SL3700-0LG41-6AA3
1600
2000
6SL3700-0LG42-0BA3
6SL3700-0LG42-5BA3
2500
6SL3700-0LG43-2BA3
3200
Parallel connection of two Line Modules with identical output rating.
The required derating factors listed below are already included in the current values given above:
- 7.5 % for Basic Line Modules
- 7.5 % for Smart Line Modules
- 5 %
for Active Line Modules
1)
The listed current values are based on an ambient temperature (inlet air temperature) of 40 °C
Basic Line Modules
Current.
Order No.
[AC]
A
365
6SL3730-1TE34-2AA3
6SL3730-1TE35-3AA3
460
6SL3730-1TE38-2AA3
710
6SL3730-1TE41-2AA3
1010
6SL3730-1TE41-5AA3
1265
1630
6SL3730-1TE41-8AA3
2 x 935
6SL3730-1TE41-2BA3
6SL3730-1TE41-2BC3
2 x 1170 6SL3730-1TE41-5BA3
6SL3730-1TE41-5BC3
2 x 1508 6SL3730-1TE41-8BA3
6SL3730-1TE41-8BC3
6SL3730-1TG33-0AA3
260
375
6SL3730-1TG34-3AA3
575
6SL3730-1TG36-8AA3
925
6SL3730-1TG41-1AA3
1180
6SL3730-1TG41-4AA3
6SL3730-1TG41-8AA3
1580
2 x 855
6SL3730-1TG41-1BA3
6SL3730-1TG41-1BC3
2 x 1092 6SL3730-1TG41-4BA3
6SL3730-1TG41-4BC3
2 x 1462 6SL3730-1TG41-8BA3
6SL3730-1TG41-8BC3
SINAMICS S120 Cabinet Modules
Engineering Information
Smart Line Modules
Current.
Order No.
[AC]
A
463
6SL3730-6TE35-5AA3
6SL3730-6TE37-3AA3
614
883
6SL3730-6TE41-1AA3
6SL3730-6TE41-3AA3
1093
6SL3730-6TE41-7AA3
1430
2 x 817
6SL3730-6TE41-1BA3
6SL3730-6TE41-1BC3
2 x 1011 6SL3730-6TE41-3BA3
6SL3730-6TE41-3BC3
2 x 1323 6SL3730-6TE41-7BA3
6SL3730-6TE41-7BC3
463
6SL3730-6TG35-5AA3
6SL3730-6TG38-8AA3
757
1009
6SL3730-6TG41-2AA3
6SL3730-6TG41-7AA3
1430
2 x 700
6SL3730-6TG38-8BA3
6SL3730-6TG38-8BC3
2 x 934
6SL3730-6TG41-2BA3
6SL3730-6TG41-2BC3
2 x 1323 6SL3730-6TG41-7BA3
6SL3730-6TG41-7BC3
SINAMICS Engineering Manual – November 2015
Active Line Modules
Current.
Order No.
[AC]
A
6SL3730-7TE32-1BA3
210
260
6SL3730-7TE32-6BA3
380
6SL3730-7TE33-8BA3
6SL3730-7TE35-0BA3
490
6SL3730-7TE36-1BA3
605
840
6SL3730-7TE38-4BA3
6SL3730-7TE41-0BA3
985
6SL3730-7TE41-4BA3
1405
2 x 936
6SL3730-7TE41-0BA3
6SL3730-7TE41-0BC3
2 x 1335 6SL3730-7TE41-4BA3
6SL3730-7TE41-4BC3
575
6SL3730-7TG35-8BA3
6SL3730-7TG37-4BA3
735
1025
6SL3730-7TG41-0BA3
6SL3730-7TG41-3BA3
1270
2 x 698
6SL3730-7TG37-4BA3
6SL3730-7TG37-4BC3
2 x 974
6SL3730-7TG41-0BA3
6SL3730-7TG41-0BC3
2 x 1206 6SL3730-7TG41-3BA3
6SL3730-7TG41-3BC3
413/528
Ó Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150