The teleservice connection enables staff at the service center to perform all control and setting
functions with the STARTER software for the purpose of providing servicing support. The
teleservice connection requires a suitable modem which can establish a communication link
between the internal PROFIBUS and the service center over a telephone line. This modem
with PROFIBUS link is integrated in the SIMATIC TS Adapter II. An extension cable may be
needed to make the connection to the telephone line. In addition, a 24 VDC supply voltage for
the TS Adapter must be provided on-site.
3.6.12

1x temperature sensor evaluation unit TM150 (option G51)

This option comprises a temperature sensor evaluation unit TM150.
Terminal Module TM150 is used for sensing and evaluating several temperature sensors.
Terminal Module TM150 is designed to connect a maximum of 12 temperature sensors.
For more information, see document "Supplementary component descriptions".
3.6.13

Additional Terminal Module TM31 (option G61)

One TM31 and two TM15 Terminal Modules are already part of each standard variant of the
drive. The Terminal Modules are used for the following functions:
● Inclusion of warning and fault messages and control signals
● Communication with a higher-level control level.
If the number of signals to be monitored is insufficient, the interface can be extended to include
an additional Terminal Module. Additional digital inputs and outputs and two analog inputs and
outputs are available with the TM31. The inputs and outputs are used, for example, for fetching
temperatures.
The TM31 Terminal Module provides the following inputs and outputs:
● 8 digital inputs
● 4 bidirectional digital inputs and outputs
● 2 relay outputs with changeover contact
● 2 analog inputs
● 2 analog outputs
● 1 temperature sensor input (KTY84-130/PTC)
When the analog inputs and outputs on the optional TM31 are used for communicating with
the control level, additional isolating transformers are available (optional).
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017
Note
The second TM31 must be connected at the plant site.
The default setting of the inputs/outputs is not provided by the factory and must be
undertaken according to the requirements of the respective plant during commissioning.