Siemens SINAMICS G130 Engineering Manual page 355

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS S120
Engineering Information
DRIVE-CLiQ connections between the Active Line Module of frame size GX and the Motor Modules of frame size FX
Longer DRIVE-CLiQ cables will be required to bridge cabinet cross-beams, to link Motor Modules which are not
mounted flush with one another, or to link combinations of Motor Modules in frame sizes FX and GX (please note the
differences in depth between these frame sizes). These cable lengths can be calculated using the formulae given in
the picture.
A distance X of about 70 mm can be bridged with the supplied cable [3] in order to connect an Active Line Module in
frame size GX with a Motor Module in frame size FX. The same cable can bridge a distance X of about 270 mm to
make a connection between modules of the same frame size, as these are of the same depth.
The 0.6 m DRIVE-CLiQ cable supplied with the Motor Module is too short as cable [4] to bridge distance Y. The next-
longer pre-assembled DRIVE-CLiQ cable in the catalog, 0.95 m in length, will normally be used for this purpose.
The 0.95 m DRIVE-CLiQ cable can also be used to link Motor Modules of different frame sizes, i.e. FX and GX
(please note the difference in depth of 200 mm between frame sizes FX and GX).
This cable is shown as cable [2] in the picture below.
SINAMICS Engineering Manual – November 2015
355/528