Note:
By contrast with the S120 Line Modules and S120 Motor Modules of the SINAMICS S120 modular system (Chassis
and Cabinet Modules) with which a parallel connection can be created using up to four identical individual modules,
the G150 parallel converter is a ready-to-connect converter cabinet unit which is constructed of two lower-output
SINAMICS G150 converter cabinet units or of two Basic Line Modules and two or three Motor Modules. The parallel
converter is ordered as a unit under a single order number. The technical data stated in the catalogs and the tables in
this engineering manual therefore generally refer to the complete G150 parallel converter and already include the
current and power derating factors required for parallel connections. Owing to the length dimensions of the parallel
converters, the G150 is delivered in transport units.
The following table shows the power spectrum of SINAMICS G150 parallel converters. The last column of the table
states (for information only) the individual components from which the relevant parallel converters are built.
Rated
Low overload
output current
P
L
[A]
[kW]
Line supply voltage 380 V – 480 V 3AC
1120
630
1380
710
1560
900
Line supply voltage 500 V – 600 V 3AC
860
630
1070
710
1360
1000
Line supply voltage 660 V – 690 V 3AC
1070
1000
1360
1350
1500
1500
1729
1750
1948
1950
2158
2150
2413
2400
2752
2700
Power spectrum of SINAMICS G150 parallel converters
Since all SINAMICS G150 parallel converters always consist of two identical rectifiers on the line side, the rectifiers
can operate as either a 6-pulse or a 12-pulse bridge circuit. The harmonic effects on the supply system are
significantly lower in 12-pulse operation than in 6-pulse operation (see section "Harmonic effects on supply system" in
chapter "Fundamental Principles and System Description").
Different decoupling measures need to be considered on the line side depending on whether the parallel connection
is a 6-pulse or 12-pulse circuit.
Different decoupling measures also need to be considered on the motor side depending on the type of winding
system of the motor (electrically isolated winding systems or one common winding system) and the number of
inverters in the G150 parallel connection (two or three).
For this reason, the boundary conditions to be considered at the line side and the motor side are discussed in more
detail below.
SINAMICS Engineering Manual – November 2015
326/528
Ó Siemens AG
High overload
Base load
Base load
P
H
current I
current I
L
[A]
[kW]
[A]
1092
500
850
1340
560
1054
1516
710
1294
836
560
770
1036
630
950
1314
800
1216
1036
900
950
1314
1200
1216
1462
1350
1340
1720
1500
1547
1940
1750
1742
2150
1950
1930
2390
2150
2158
2685
2400
2463
Order number
H
6SL3710-2GE41-1AA3
6SL3710-2GE41-4AA3
6SL3710-2GE41-6AA3
6SL3710-2GF38-6AA3
6SL3710-2GF41-1AA3
6SL3710-2GF41-4AA3
6SL3710-2GH41-1AA3
6SL3710-2GH41-4AA3
6SL3710-2GH41-5AA3
6SL3710-2GH41-8EA3
6SL3710-2GH42-0EA3
6SL3710-2GH42-2EA3
6SL3710-2GH42-4EA3
6SL3710-2GH42-7EA3
The parallel converter is based on
following individual components
2 x G150 / 315 kW / 605 A
2 x G150 / 400 kW / 745 A
2 x G150 / 450 kW / 840 A
2 x G150 / 315 kW / 465 A
2 x G150 / 400 kW / 575 A
2 x G150 / 500 kW / 735 A
2 x G150 / 560 kW / 575 A
2 x G150 / 710 kW / 735 A
2 x G150 / 800 kW / 810 A
2 x BLM / 1100 kW +
2 x MoMo / 900 kW / 910 A
2 x BLM / 1100 kW +
2 x MoMo / 1000 kW / 1025 A
2 x BLM / 1100 kW +
2 x MoMo / 1200 kW / 1270 A
2 x BLM / 1500 kW +
2 x MoMo / 1200 kW / 1270 A
2 x BLM / 1500 kW +
3 x MoMo / 1000 kW / 1025 A