Cable Cross-Sections And Connections On Sinamics S150 Cabinet Units; Recommended And Max. Possible Cable Cross-Sections For Line And Motor Connections - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS S150
Engineering Information

8.4 Cable cross-sections and connections on SINAMICS S150 cabinet units

8.4.1

Recommended and max. possible cable cross-sections for line and motor connections

The following tables show the recommended and maximum connectable cable cross-sections on the line and motor
sides. The recommended cross-sections are based on the fuses specified in catalog D 21.3. These are valid for PVC-
insulated, copper 3-wire cables installed horizontally in air with a permissible conductor temperature of 70 °C (e.g.
Protodur NYY or NYCWY) at an ambient temperature of 40 °C and for singly routed cables. When the conditions
differ from the above stated (cable routing, cable grouping, ambient temperature), the relevant correction factors as
stated in IEC 60364-5-52 must be applied.
When aluminum cables are used, the recommended cross-sections given in the table must be increased by a factor
of 1.3. This can be done either by enlarging the conductor cross-section or by increasing the number of parallel
cables. It is important to note, however, that the cable cross-sections must not exceed the specified maximum
permissible dimensions at the converter and must be suitable for connection to the motor terminal box.
Out-
Converter
Weight
put
SINAMICS
S150
at
(stan-
dard
400 V
model)
or
690 V
Type
[kW]
[kg]
6SL3710-...
380 V – 480 V 3AC
110
7LE32-1AA3 708
132
7LE32-6AA3 708
160
7LE33-1AA3 892
200
7LE33-8AA3 980
250
7LE35-0AA3 980
315
7LE36-1AA3 1716
400
7LE37-5AA3 1731
450
7LE38-4AA3 1778
560
7LE41-0AA3 2408
710
7LE41-2AA3 2408
800
7LE41-4AA3 2408
500 V – 690 V 3AC
75
7LG28-5AA3 708
90
7LG31-0AA3 708
110
7LG31-2AA3 708
132
7LG31-5AA3 708
160
7LG31-8AA3 892
200
7LG32-2AA3 892
250
7LG32-6AA3 892
315
7LG33-3AA3 892
400
7LG34-1AA3 1716
450
7LG34-7AA3 1716
560
7LG35-8AA3 1716
710
7LG37-4AA3 2300
800
7LG38-1AA3 2408
900
7LG38-8AA3 2408
1000
7LG41-0AA3 2408
1200
7LG41-3AA3 2408
1)
The recommendations for the North American market in AWG or MCM can be found in the corresponding standards NEC
(National Electrical Code) or CEC (Canadian Electrical Code).
SINAMICS Engineering Manual – November 2015
486/528
Ó Siemens AG
Line supply connection
Recommended
Maximum cable
1)
cross-section
cross-section
IEC
IEC
2
2
[mm
]
[mm
]
2x70
4x240
2x95
4x240
2x120
4x240
2x120
4x240
2x185
4x240
2x240
4x240
3x185
4x240
4x150
8x240
4x185
8x240
4x240
8x240
6x185
8x240
50
4x240
50
4x240
70
4x240
95
4x240
120
4x240
2x70
4x240
2x95
4x240
2x120
4x240
2x185
4x240
2x185
4x240
2x240
4x240
3x185
8x240
4x150
8x240
4x150
8x240
4x185
8x240
4x240
8x240
Motor connection
M12
Recommended
Maximum cable
1)
fixing-
cross-section
cross-section
screw
IEC
(no. of
2
[mm
]
[mm
holes)
(2)
2x50
2x150
(2)
2x70
2x150
(2)
2x95
2x150
(2)
2x95
2x150
(2)
2x150
2x240
(2)
2x185
4x240
(2)
2x240
4x240
(4)
3x185
4x240
(4)
4x185
6x240
(4)
4x240
6x240
(4)
6x185
6x240
(2)
35
(2)
50
2x150
(2)
70
2x150
(2)
70
2x150
(2)
95
2x150
(2)
120
2x150
(2)
2x70
2x185
(2)
2x95
2x240
(2)
2x120
4x240
(2)
2x150
4x240
(2)
2x185
4x240
(4)
3x150
6x240
(4)
3x185
6x240
(4)
4x150
6x240
(4)
4x185
6x240
(4)
4x240
6x240
Cabinet
grounding
M12
M12
fixing
fixing
screw
screw
IEC
(no. of
(no. of
2
]
holes)
holes)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(10)
(2)
(16)
(3)
(18)
(3)
(18)
(3)
(18)
2x70
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(3)
(18)
(3)
(18)
(3)
(18)
(3)
(18)
(3)
(18)
Re-
marks
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar
Busbar

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents