The criteria for defining of the required transformer power rating, taking into account the harmonic load as well as the
characteristics of three-winding transformers in 12-pulse operation, are described in the section "Transfomers".
1.6.3

Active Infeed

The Active Infeed is an actively pulsed, stable, regulated rectifier / regenerative unit for four-quadrant operation, i.e.
the energy flows from the supply system to the DC link and vice versa. The current values stated in the catalogs are
available in both rectifier and regenerative operation
The Active Infeed comprises a self-commutated IGBT inverter (Active Line Module ALM), which operates on the
supply system via the Clean Power Filter (Active Interface Module). The Active Line Module operates according to
the method of pulse-width modulation and generates a constant, regulated DC link voltage V
phase line voltage V
. The Clean Power Filter, which is installed between the Active Line Module and the supply
Line
system, filters out, as far as possible, the harmonics from the Active Line Module's pulse-width modulated voltage
V
, thereby ensuring a virtually sinusoidal input current on the line side and, therefore, minimal harmonic effects on
ALM
the supply system.
The Active Infeed is the highest grade SINAMICS Infeed variant. It is an integral component of SINAMICS S150
cabinet units and is available as a stand-alone Infeed of the SINAMICS S120 modular drive system in Chassis or
Cabinet Modules format.
V
Line
I
Active Interface Module AIM
Line
Clean Power Filter
Supply
SINAMICS S120 Active Infeed comprising an Active Interface Module and an Active Line Module
The Active Infeed is a self-commutated rectifier / regenerative unit and produces from the three-phase line voltage
V
a regulated DC link voltage V
Line
supply voltage dips. It operates as a step-up converter, i.e. the DC link voltage is always higher than the peak value
of the line voltage (V
DCLink
This setting should not be changed without a valid reason. Reducing the factory-set value tends to impair the control
quality while increasing it unnecessarily increases the voltage on the inverter and the motor winding. If the
permissible voltage of the motor winding is sufficiently high (see section "Increased voltage stress on the motor
winding as a result of long cables"), the DC link voltage can be increased from the factory setting to the values
V
specified in the table. This method allows a voltage higher than the line voltage to be obtained at the output of
DCmax
the inverter or Motor Module connected to the Active Infeed. The table shows the maximum achievable inverter
output voltage as a function of the DC link voltage and the modulation system used in vector control mode (space
vector modulation SVM without overmodulation or pulse-edge modulation PEM).
Supply voltage
V
Line
Units with
380 V – 480 V 3AC
Units with
500 V – 690 V 3AC
in operation with supply voltages
500 V – 600 V 3AC
660 V – 690 V 3AC
SINAMICS Active Infeed: Maximum, continuously permissible DC link voltages and attainable output voltages
Fundamental Principles and System Description
Active Infeed
which remains constant independently from line voltage variations and
DCLink,
> 1.41 • V
). The value can be parameterized (1.42 to 2.0) and its factory setting is
Line
V
DCLink
Maximum permissible DC
link voltage in steady-state
operation
V
DC max.
720 V
1000 V with V
Line
1080 V with V
Line
1080 V
V
ALM
Active Line Module ALM
I
ALM
= 1.50 • V
Line
Maximum attainable
output voltage with
space vector
modulation
V
out max SVM
504 V
= 500 V
700 V with V
Line
= 600 V
756 V with V
Line
756 V
SINAMICS Engineering Manual – November 2015
Engineering Information
from the three-
DCLink
V
DC Link
DC Link
Maximum attainable
output voltage with
pulse-edge modulation
V
out max. PEM
533 V
= 500 V
740 V with V
= 500 V
Line
= 600 V
800 V with V
= 600 V
Line
800 V
105/528