Siemens SINAMICS G130 Engineering Manual page 213

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Ambient
temperature
10 ℃
T
20 %
a
20 ℃
< 0 °C
< 0 ℃
25 ℃
0.6 ℃
30 ℃
4.7 ℃
35 ℃
8.7 ℃
40 ℃
45 ℃
12.8℃
50 ℃
16.8℃
20.8℃
Dew point T
as a function of ambient temperature T
dp
According to the table above, the difference between the dew point T
virtually constant for a given relative air humidity Φ when the ambient temperature T
temperature rises, the difference between the dew point T
particularly under conditions of relatively low air humidity.
As a result of this correlation, it is possible to use the 3rd line from the above table (applicable to an ambient
temperature of 25°C) in order to calculate the temperature difference ΔT
in order to keep the coolant temperature setpoint T
ambient air.
Relative air humidity Φ
20 %
Dew point at ambient
0.6℃
temperature of 25℃
Difference between dew
point and ambient
-24.4℃
temperature T
– T
dp
a
Addition of 4°C as
safety margin to the
-20.4℃
dew point:
ΔT
= (T
– T
) + 4°C
L
dp
a
Calculation of the temperature difference ΔT
condensation
The diagram below shows the temperature difference ΔT
air according to the last line in the table above.
Temperature difference ΔT
L
Fundamental Principles and System Description
< 0 ℃
< 0 ℃
0.2 ℃
30 %
40 %
50 %
2.0 ℃
6.0 ℃
9.3 ℃
6.3 ℃
10.5℃
13.8℃
10.5°C
14.9℃
18.4℃
14.8℃
19.3℃
22.9℃
19.1℃
23.7℃
27.5℃
23.3℃
28.2℃
32.0℃
27.5℃
32.6℃
36.6℃
and relative air humidity Φ
a
30 %
40 %
50 %
10.5°C
13.8°C
6.3℃
-18.7℃
-14.5℃
-11.2℃
-14.7℃
-10.5℃
-7.2℃
that must be added to the ambient temperature T
L
as a function of relative air humidity Φ
Relative air humidity Φ
2.7 ℃
4.8 ℃
6.7 ℃
60 %
70 %
80 %
12.0℃
14.3℃
16.4℃
16.7℃
19.1℃
21.2℃
21.3℃
23.8℃
26.1℃
26.0℃
28.6℃
30.9℃
30.6℃
33.4℃
35.8℃
35.3℃
38.1℃
40.6℃
40.0℃
42.9℃
45.5℃
and the ambient temperature T
dp
and the ambient temperature T
dp
to be added to the ambient temperature T
L
always at least 3°C to 5°C higher than the dew point of the
set
60 %
70 %
80 %
16.7°C
21.2°C
19.1℃
-8.3℃
-5.9℃
-3.8℃
-4.3℃
-1.9℃
+0.2℃
as a function of the relative air humidity Φ of the ambient
L
SINAMICS Engineering Manual – November 2015
Engineering Information
7.6 ℃
8.4 ℃
9.2 ℃
85 %
90 %
95 %
17.4℃
18.3℃
19.1℃
22.2℃
23.2℃
24.1℃
27.1℃
28.1℃
29.0℃
32.0℃
33.0℃
34.0℃
36.9℃
37.9℃
38.9℃
41.8℃
42.9℃
43.9℃
46.6℃
47.8℃
48.9℃
a
is ≤ 25°C. As the ambient
a
increases slightly,
a
85 %
90 %
95 %
22.2°C
23.2°C
24.1°C
-2.8℃
-1.8℃
-0.9℃
+1.2℃
+2.2℃
+3.1℃
in order to prevent
a
213/528
Ó Siemens AG
100 %
10.0℃
20.0℃
24.9℃
29.9℃
34.9℃
39.9℃
44.9℃
49.9℃
remains
a
100 %
24.9°C
-0.1℃
+3.9℃