7.2.8.3

Parallel connections of Motor Modules

7.2.8.3.1 General

Motor Modules connected in parallel must always be identical in terms of type, voltage rating and power rating. If
SINAMICS S120 Motor Modules are connected in parallel, imbalances in current distribution can occur despite the
current compensation control. This means that a current derating factor of 5 % must be applied to parallel
connections.
In the case of motors with a common winding system, it is important to observe the specified minimum cable lengths
between the Motor Modules and the motor in order to ensure that the parallel-connected Motor Modules are
decoupled. If it is not possible to realize cabling with the minimum required cable length, motor reactors or filters must
be installed.
For detailed information on the subject of parallel converters, refer to section "Parallel connections of converters" in
chapter "Fundamental Principles and System Description".

7.2.8.3.2 Minimum motor cable lengths for motors with common winding system

The table below specifies the minimum required motor cable lengths for parallel connections of SINAMICS S120
Motor Modules in air-cooled Cabinet Modules format, whereby the given length is the distance between the output of
each Motor Module and the motor terminal box as measured along the motor cable.
Motor Module
P
at 400V
rated
Frame size
[kW]
Supply voltage 510 V – 720 V DC
FX
110
FX
132
GX
160
GX
200
GX
250
HX
315
HX
400
HX
450
JX
560
JX
710
JX
800
Motor Module
P
at 500V
rated
Frame size
[kW]
Supply voltage 675 V – 900 V DC
FX
55
FX
55
FX
75
FX
90
GX
110
GX
132
GX
160
GX
200
HX
250
HX
315
HX
400
JX
500
JX
560
JX
630
JX
710
JX
900
1)
permissible tolerance: –20 %
2)
These values apply to Motor Modules with line supply voltages of 500 V to 690 V 3AC (order number 6SL3720-1TGxx-xAA3).
Min. cable lengths for parallel connections of S120 Motor Modules connected to motors with a common winding system
Motor supply cable
1)
I
Minimum length
rated
[A]
[m]
210
30
260
27
310
20
380
17
490
15
605
13
745
10
840
9
985
8
1260
6
1405
5
Motor supply cable Motor Module
1)
I
Minimum length
rated
[A]
[m]
2)
85
80
100
72
120
65
150
55
175
50
215
40
260
32
330
25
410
20
465
18
575
15
735
13
810
11
910
10
1025
8.5
1270
7
SINAMICS Engineering Manual – November 2015
SINAMICS S120 Cabinet Modules
Engineering Information
P
at 690V
Frame size
rated
[kW]
Supply voltage 890 V – 1035 V DC
FX
75
FX
90
FX
110
FX
132
GX
160
GX
200
GX
250
GX
315
HX
400
HX
450
HX
560
JX
710
JX
800
JX
900
JX
1000
JX
1200
Motor supply cable
I
Minimum length
rated
[A]
[m]
2)
85
100
100
90
120
80
150
70
175
60
215
50
260
40
330
30
410
25
465
25
575
20
735
18
810
15
910
12
1025
10
1270
8
427/528