Fundamental Principles and System Description
Engineering Information
flow speeds inside the hood without taking into account other cabinet internals such as additional electronic boards,
busbars and fuses. If several devices are installed in one cabinet, the required volumetric flow rate corresponds to
the sum of the flow rates required for the individual components. If multiple hoods are interconnected, the total
volumetric flow rate must be calculated as well and a suitable fan selected accordingly.
Output
Frame
power
size
[ kW ]
Power Modules / 380 V – 480 V 3AC
110
FL
132
FL
160
GL
250
GL
Basic Line Modules / 380 V – 480 V 3AC
360
FBL
600
FBL
830
GBL
Basic Line Modules / 500 V – 690 V 3AC
355
FBL
630
FBL
1100
GBL
1370
GBL
Active Line Modules / 380 V – 480 V 3AC
300
GXL
380
HXL
500
HXL
630
JXL
900
JXL
Active Line Modules / 500 V – 690 V 3AC
630
HXL
800
HXL
900
HXL
1100
JXL
1400
JXL
1700
JXL
Motor Modules / 380 V – 480 V 3AC / 510 V – 720 V DC
110
FXL
132
FXL
160
GXL
250
GXL
315
HXL
400
HXL
450
HXL
560
JXL
710
JXL
800
JXL
800
JXL
Motor Modules / 500 V – 690 V 3AC / 675 V – 1035 V DC
90
FXL
132
FXL
200
GXL
315
GXL
450
HXL
560
HXL
710
HXL
800
HXL
800
JXL
1000
JXL
1200
JXL
1500
JXL
Required volumetric flow rates dV/dt of hood-mounted fan in cabinets with degree of protection of > IP21
Fan type W2E200-HH38-01 supplied by EBM-Papst is recommended for use as a hood-mounted fan.
SINAMICS Engineering Manual – November 2015
224/528
Ó Siemens AG
Rated
Required volumetric flow rate
output current
dV/dt of hood fan
[ A ]
210 (AC)
260 (AC)
310 (AC)
490 (AC)
740 (DC)
1220 (DC)
1730 (DC)
420 (DC)
730 (DC)
1300 (DC)
1650 (DC)
549 (DC)
677 (DC)
941 (DC)
1100 (DC)
1573 (DC)
644 (DC)
823 (DC)
907 (DC)
1147 (DC)
1422 (DC)
1740 (DC)
210 (AC)
260 (AC)
310 (AC)
490 (AC)
605 (AC)
745 (AC)
840 (AC)
985 (AC)
1260 (AC)
1330 (AC)
1405 (AC)
100 (AC)
150 (AC)
215 (AC)
330 (AC)
465 (AC)
575 (AC)
735 (AC)
810 (AC)
810 (AC)
1025 (AC)
1270 (AC)
1560 (AC)
3
[ m
/ s ]
0.003
0.003
0.004
0.006
0.010
0.017
0.024
0.009
0.016
0.018
0.023
0.006
0.007
0.010
0.020
0.026
0.007
0.018
0.018
0.021
0.024
0.038
0.002
0.003
0.004
0.006
0.007
0.009
0.010
0.020
0.024
0.026
0.026
0.002
0.003
0.004
0.005
0.006
0.007
0.018
0.018
0.019
0.021
0.024
0.038
Average flow speed
[ m / s ]
0.01
0.02
0.02
0.03
0.05
0.09
0.12
0.05
0.08
0.09
0.12
0.03
0.04
0.05
0.10
0.14
0.04
0.10
0.10
0.11
0.12
0.21
0.01
0.02
0.02
0.03
0.04
0.05
0.05
0.10
0.12
0.14
0.14
0.01
0.02
0.02
0.03
0.04
0.04
0.10
0.10
0.10
0.11
0.12
0.21