1.10.4

Comparison of the properties of the motor-side reactors and filters

The table below provides an overview of the key properties of the motor-side reactors and filters.
Converter output:
Voltage rate-or-rise dv/dt
at the motor terminals
Peak voltage V
PP
at the motor terminals
Permitted
pulse modulation systems
Permitted
pulse frequencies
Permitted
output frequencies
Permitted
control modes
Control quality and
dynamic response
Stray losses
in reactor or filter
relative to converter
losses in rated operation
Stray losses in motor
due to converter supply
relative to rated operation
Reduction in motor noise
caused by converter
Reduction in bearing currents
in the motor
Max. cable length shielded
Max. cable length unshielded
Volume
Price
Comparison of the key propertiesof motor-side reactors and filters
Fundamental Principles and System Description
Without
With
reactor or filter
motor reactor
High
(see chart
(see chart
on next page)
on next page)
High
Relatively high
(see chart
(see chart
on next page)
on next page)
No restrictions
No restrictions
No restrictions
≤ 2x factory setting
No restrictions
≤ 150 Hz
Servo control
Servo control
Vector control
Vector control
V/f control
V/f control
Very high
Approx. 10 %
Approx. 10 %
Approx. 10 %
No
No
300 m
450 m
SINAMICS Engineering Manual – November 2015
Engineering Information
With
dv/dt filter
Medium
Low
(see chart
on next page)
Low
(see chart
on next page)
No restrictions
≤ 2x factory setting
≤ 150 Hz
Servo control
Vector control
V/f control
High
High
Approx. 10 – 15 %
Approx. 10 %
Minimal
Minimal
Medium
Yes
300 m
100 m or 300 m
450 m
150 m or 450 m
Low
Medium
Low
Medium to high
Ó Siemens AG
With
sine-wave filter
Very low
(see chart
on next page)
Very low
(see chart
on next page)
Space vector
modulation SVM only
Exactly 2x factory
setting
≤ 150 Hz
Vector control
V/f control
Low
Approx. 10 – 15 %
Very low
Significant
Yes
300 m
450 m
Medium
High