5.4 Cable cross-sections and connections on SINAMICS G150 Cabinet Units

5.4.1

Recommended and max. possible cable cross-sections for line and motor connections

The tables below list the recommended and the maximum connectable cable cross-sections on the line and motor
sides for single converters (versions A and C) and for parallel connections of converters (version A). The
recommended cross-sections are based on the fuses specified in catalog D 11. These are valid for PVC-insulated,
copper 3-wire cables installed horizontally in air with a permissible conductor temperature of 70 °C (e.g. Protodur
NYY or NYCWY) at an ambient temperature of 40 °C and for singly routed cables. When the conditions differ from
the above stated (cable routing, cable grouping, ambient temperature), the relevant correction factors as stated in
IEC 60364-5-52 must be applied.
When aluminum cables are used, the recommended cross-sections given in the table must be increased by a factor
of 1.3. This can be done either by enlarging the conductor cross-section or by increasing the number of parallel
cables. It is important to note, however, that the cable cross-sections must not exceed the specified maximum
permissible dimensions at the converter and must be suitable for connection to the motor terminal box.
Single converters G150 Version A
Out-
Converter
Weight
put
SINAMICS
G150
(stan-
Version A
dard
model)
Type
[kW]
[kg]
6SL3710-...
380 V – 480 V 3AC
110
1GE32-1AA3 320
132
1GE32-6AA3 320
160
1GE33-1AA3 390
200
1GE33-8AA3 480
250
1GE35-0AA3 480
315
1GE36-1AA3 860
400
1GE37-5AA3 865
450
1GE38-4AA3 1075
560
1GE41-0AA3 1360
500 V – 600 V 3AC
110
1GF31-8AA3 390
132
1GF32-2AA3 390
160
1GF32-6AA3 390
200
1GF33-3AA3 390
250
1GF34-1AA3 860
315
1GF34-7AA3 860
400
1GF35-8AA3 865
500
1GF37-4AA3 1320
560
1GF38-1AA3 1360
660 V – 690 V 3AC
75
1GH28-5AA3 320
90
1GH31-0AA3 320
110
1GH31-2AA3 320
132
1GH31-5AA3 320
160
1GH31-8AA3 390
200
1GH32-2AA3 390
250
1GH32-6AA3 390
315
1GH33-3AA3 390
400
1GH34-1AA3 860
450
1GH34-7AA3 860
560
1GH35-8AA3 860
710
1GH37-4AA3 1320
800
1GH38-1AA3 1360
Line supply connection
Recommended
Maximum cable
1)
cross-section
cross-section
IEC
IEC
2
2
[mm
]
[mm
]
2x70
4x240
2x95
4x240
2x120
4x240
2x120
4x240
2x185
4x240
2x240
4x240
3x185
4x240
4x150
8x240
4x185
8x240
120
4x240
2x70
4x240
2x95
4x240
2x120
4x240
2x185
4x240
2x185
4x240
2x240
4x240
3x185
8x240
4x150
8x240
50
4x240
50
4x240
70
4x240
95
4x240
120
4x240
2x70
4x240
2x95
4x240
2x120
4x240
2x185
4x240
2x185
4x240
2x240
4x240
3x185
8x240
4x150
8x240
Motor connection
M12
Recommended
Maximum cable
1)
fixing
cross-section
cross-section
screw
IEC
IEC
(no. of
2
holes)
[mm
]
(2)
2x50
(2)
2x70
(2)
2x95
(2)
2x95
(2)
2x150
(2)
2x185
(2)
2x240
(4)
3x185
(4)
4x185
(2)
95
(2)
120
(2)
2x70
(2)
2x95
(2)
2x120
(2)
2x150
(2)
2x185
(4)
2x240
(4)
3x185
(2)
35
(2)
50
(2)
70
(2)
70
(2)
95
(2)
120
(2)
2x70
(2)
2x95
(2)
2x120
(2)
2x150
(2)
2x185
(4)
3x150
(4)
3x185
SINAMICS Engineering Manual – November 2015
SINAMICS G150
Engineering Information
Cabinet
grounding
M12 fixing
M12 fixing
screw
screw
(no. of
(no. of
2
holes)
holes)
[mm
]
2x150
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x240
(2)
(2)
4x240
(2)
(2)
4x240
(2)
(10)
4x240
(2)
(16)
6x240
(3)
(18)
2x150
(2)
(2)
2x150
(2)
(2)
2x185
(2)
(2)
2x240
(2)
(2)
4x240
(2)
(2)
4x240
(2)
(2)
4x240
(2)
(2)
6x240
(3)
(18)
6x240
(3)
(18)
2x70
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x150
(2)
(2)
2x185
(2)
(2)
2x240
(2)
(2)
4x240
(2)
(2)
4x240
(2)
(2)
4x240
(2)
(2)
6x240
(3)
(18)
6x240
(3)
(18)