Siemens SINAMICS G130 Engineering Manual page 168

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Fundamental Principles and System Description
Engineering Information
2
The I
t value, averaged over a load duty cycle duration T of max. 300 s, must not exceed the 100 % value. The
exeptions are stated in the table.
For the following SINAMICS converters or Motor Modules the permissible I
100 % with load duty cycles:
Converter
Line
or
volt-
Motor Module
age
SINAMICS G and S
400 V
SINAMICS G and S
400 V
SINAMICS G and S
400 V
SINAMICS G and S
400 V
SINAMICS G and S
400 V
SINAMICS S 4AS3
400 V
2
The I
t value is the criterion for losses and temperature rise in the power unit during the load duty cycle and is defined
as follows:
Key to equation:
·
I(t)
RMS value of the output current of the converter or inverter as a function of time
(In the case of parallel connections of S120 Motor Modules, I(t) is the RMS value of the output
current of a partial inverter resp. one Motor Module.)
·
I
Rated output current of the converter or inverter
Rated
(In the case of parallel connections of S120 Motor Modules, I
partial inverter resp. one Motor Module, not taking into account the derating factor for parallel
operation.)
·
k
Current derating factor (total derating factor; see above for definition)
D
·
T
Load duty cycle duration which must not exceed the 300 s value for the standard load duty cycle
For the practical calculation of the I
current in each case as an approximate substitute to the output current time characteristic required by the application.
This simplifies the calculation as the integration is replaced by a simple summation.
1
2
=
t I
value
T
i.e. the sum of all phases T
below illustrates the correlations.
Approximation of the current characteristic over time using time phases with constant current
SINAMICS Engineering Manual – November 2015
168/528
Ó Siemens AG
Permissible
Output
Output
2
I
t value
rat-
current
with load
ing
duty cycles
110 kW
210 A
90 %
315 kW
605 A
72 %
400 kW
745 A
73 %
450 kW
840 A
87 %
560 kW
985 A
95 %
800 kW
1330 A
93 %
1
2
=
×
t I
value
T
2
t value, it is generally helpful to apply a finite number m of phases of constant
é
2
æ
ö
æ
I
ç ç
÷ ÷
ç ç
ê
×
×
+
1
T
1
×
I
k
I
ê
è
ø
è
ë
Rated
D
Rated
where
to T
equals the load duty cycle duration T, where T must be ≤ 300 s. The diagram
1
m
2
t value is limited to values of less than
Converter
Line
or
volt-
Motor Module
age
SINAMICS G
400 V
SINAMICS G
400 V
SINAMICS G
400 V
SINAMICS G + S
500 V
SINAMICS G + S
690 V
SINAMICS S LC
690 V
2
æ
ö
T
t I
) (
ò
ç ç
÷ ÷
dt
• 100 %
×
I
k
è
ø
Rated
D
0
Rated
2
ö
æ
I
÷ ÷
ç ç
×
+
+
2
T
......
2
×
k
I
ø
è
D
m
å
=
T
T
,
m
1
Output
Output
rat-
current
ing
630 kW
1120 A
710 kW
1380 A
900 kW
1560 A
200 kW
330 A
315 kW
330 A
1500kW
1560 A
is the rated output current of a
ù
2
ö
I
÷ ÷
ú
×
n
T
100 %
m
×
k
ú
ø
û
Rated
D
Permissible
2
I
t value
with load
duty cycles
72 %
73 %
86 %
90 %
90 %
85 %

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents