Siemens SITRANS FC430 Operating Instructions Manual page 62

Coriolis flowmeters with hart
Hide thumbs Also See for SITRANS FC430:
Table of Contents

Advertisement

Connecting
5.5 Step 1: Connecting the DSL and the transmitter
8. Connect wires to terminals according to list below.
9. Ensure the DIP switches are all set to OFF.
10.Reinstate DSL cassette including mounting screw.
11.Connect sensor connection and sensor cable plugs.
12.Restore flexible strap around all wires.
13.Assemble and tighten cable gland.
14.Remove O-ring from DSL lid.
15.Reinstate lid and screw in until mechanical stop. Wind back lid by one turn.
16.Mount O-ring by pulling it over the DSL lid and tighten lid until you feel friction from the O-
ring on both sides. Wind lid further by one quarter of a turn to seal on the O-ring.
17.Reinstate and tighten lid lock screw.
18.Close and secure DSL lid including lock screw. Turn the lid until you can feel the friction
of the O-ring. From this point turn the lid ¼ turn to be tight.
60
Terminal number
1
2
3
4
Description
+15 VDC
0 VDC
B
A
Operating Instructions, 05/2015, A5E03361511-AF
Wire color (Siemens cable)
Orange
Yellow
White
Blue
FC430 with HART