Default settings
C.4 Inputs/Outputs
HMI menu ID
Parameter
2.4.2.19
Process Value
2.4.2.20
Direction
2.4.2.21
Pulse Width
2.4.2.22
Pulse Width Unit
2.4.2.23
Pulse Unit
2.4.2.23
Pulse Unit
2.4.2.23
Pulse Unit
2.4.2.24
Amount Per Pulse
2.4.2.24
Amount Per Pulse
2.4.2.24
Amount Per Pulse
2.4.2.25
Polarity
282
Description
Select process value for pulse
output.
Select measured flow direction.
The flowmeter will only output
pulses when flow value is
measured in selected direction.
Define the pulse duration. Long
duration pulses can overlap at
high flow rate.
Set the time unit for configuring
pulse width.
Select unit for pulse output. Unit
is not applied at communication
interface.
Select unit for pulse output. Unit
is not applied at communication
interface.
Select unit for pulse output. Unit
is not applied at communication
interface.
Define the quantity represented
by each pulse.
Define the quantity represented
by each pulse.
Define the quantity represented
by each pulse.
Set the level of an active pulse.
Default value
Value range
[unit]
Massflow
Massflow
•
Volumeflow
•
Corrected
•
Volumeflow
•
Fraction A
•
Fraction B
•
Positive
Positive
•
Negative
•
Bidirectional
•
0.1
0.00004 to 4.0
[s]
s
s
•
ms
•
µs
•
kg
g
•
kg
•
t
•
lb
•
STon
•
oz
•
T
•
L
L, hL, m³, Ugal,
BL, BB, BO, in³,
ft³, yd³, gal, bush
NL
NL
•
Nm³
•
SL
•
Sft³
•
Sm³
•
1.0
[kg]
0.001
[m
]
3
1.0
[normal m
]
3
Active High
Active High
•
Level
Level
Active Low
•
Level
Operating Instructions, 05/2015, A5E03361511-AF
Access
level
User
User
User
User
User
User
User
User
User
User
User
FC430 with HART