Installation variations
Note
Requirements for safe installation
• Remote sensor FCS400 can be installed in Zone 1, Div. 1 as Intrinsically Safe or
Flameproof.
• Standard remote installation with FCT030 because the connection is certified Intrinsically
Safe. however flameproof seals and conduit (for IS cable) can be used.
• Requirement for IS circuit is that the maximum input voltage Vi to DSL is 20 VDC, Ii is
maximum 484 mA, Pi < 2.3 W
• In Ex d installation Um is 24 VDC
Maximum temperature specifications for Ex use
FCS400 remote sensor with DSL
Temperature classification with and without dust is related to the process temperature and
ambient temperature as listed below.
The maximum allowable process fluid temperatures with respect to temperature class for the
device when used with potentially explosive gases in a maximum ambient temperature of
+60°C are:
If the equipment is placed in a "tb" environment (Zone 21), the maximum process
temperatures shall be as follows:
FC430 with HART
Operating Instructions, 05/2015, A5E03361511-AF
Ta (°C)
Maximum Process Temperature per Temperature Class (°C)
T6
60
70
55
85
50
85
45
85
40
85
35
85
30
85
Ta (°C)
60
55
50
45
40
35
30
2.2 Installation in hazardous locations
T5
T4
70
70
100
100
100
130
100
135
100
135
100
135
100
135
Maximum Process Temperature per Temperature
Class (°C)
Safety notes
T3
70
100
130
160
190
200
200
70
100
130
160
190
200
200
25