Commissioning
6.4 Commissioning with PDM
4. Select Device → Wizard → Zero Point Adjustment... from the main menu of SIMATIC PDM
to perform an automatic zero point adjustment.
5. Click Next and then Auto Zero Point Adjust.
6. During the process a progress bar is visible.
7. At the end of the zero adjustment, the outcome is displayed as an offset and a standard
deviation.
Note
If you get an error message after the zero point adjustment, refer to Alarms and system
messages (Page 171).
The system is now ready for normal operation.
106
Operating Instructions, 05/2015, A5E03361511-AF
FC430 with HART