LOGO! functions

4.4.20 Analog amplifier

Short description
This special function amplifies the value of an analog input
and outputs the result at an analog output.
Symbol in
LOGO!
*
AI1...AI8: 0...10 V corresponds with 0...1000 (internal value).
Gain and offset parameters
Please note the information on gain and offset parameters
in Chapter 4.3.6.
Parameter p (number of decimals)
Applies only to the AQ value in a message text.
196
Wiring
Input Ax
You apply the analog signal to
be amplified at input Ax.
Use the analog inputs AI1...AI8
(
)
*
, the analog flags
AM1...AM6, the block number
of a function with analog out-
put, or the analog outputs AQ1
and AQ2.
Parameter
A: Gain
B: Zero offset
p:
Output AQ
This special function has an
analog output! This output can
only be connected with the
analog input of a function, an
analog flag or an analog output
connector (AQ1, AQ2).
Range of values for AQ:
–32768...+32767
Description
Range of values:
10.00
Range of values: 10.000
Number of decimals
Range of values:
0, 1, 2, 3
LOGO! Manual
A5E00380835-01