LOGO! installation and wiring

2.3.2 Connecting LOGO! inputs

Requirements
At the inputs you connect sensor elements such as:
momentary switches, switches, light barriers, daylight
control switches etc.

Sensor characteristics for LOGO!

Signal status 0
Input current
Signal status 1
Input current
Signal status 0
Input current
Signal status 1
Input current
Signal status 0
Input current
Signal status 1
Input current
32
LOGO! 12/24 RC/RCo
LOGO! DM8 12/24 R
I1 ... I6
< 5 VDC
< 5 VDC
< 1.0 mA
< 0.05 mA
> 8 V DC
> 8 V DC
> 1.5 mA
> 0.1 mA
LOGO! 24
LOGO! 24
RC/RCo (AC)
RC/RCo (DC)
LOGO! DM8
LOGO! DM8
24 R (AC)
24 R (DC)
< 5 V AC
< 5 V DC
< 1.0 mA
< 1.0 mA
> 12 V AC
> 12 V DC
> 2.5 mA
> 2.5 mA
LOGO! DM16
LOGO! DM16
24 R
< 5 V DC
< 5 V DC
< 1.0 mA
< 1.0 mA
> 12 V DC
> 12 V DC
> 2.0 mA
> 2.0 mA
LOGO! DM8 24
I7, I8
I1 ... I6
< 5 VDC
< 1.0 mA
> 8 V DC
> 1.5 mA
LOGO! 230
RC/RCo (AC)
LOGO! DM8
230 R (AC)
< 40 V AC
< 003 mA
> 79 V AC
> 0.08 mA
LOGO! DM16
24
230 R (AC)
< 40 V AC
< 0.05 mA
> 79 V AC
> 0.08 mA
LOGO! 24/24o
I7, I8
< 5 VDC
< 0.05 mA
> 8 V DC
> 0.1 mA
LOGO! 230
RC/RCo (DC)
LOGO! DM8
230 R (DC)
< 30 V DC
< 003 mA
> 79 V DC
> 0.08 mA
LOGO! DM16
230 R (DC)
< 30 V DC
< 0.05 mA
> 79 V DC
> 0.08 mA