Siemens Logo! Manual page 276

Hide thumbs Also See for Logo!:
Table of Contents

Advertisement

Technical data
Criterion
Ambient mechanical conditions
Protection mode
Vibrations:
Shock
Drop
Free fall (packaged)
Electromagnetic compatibility (EMC)
Noise emission
Electrostatic discharge
Electromagnetic fields
HF currents on cables and
cable shielding
Burst pulses
High-energy surge pulse
(applies only to
LOGO! 230 ...)
Safety to IEC / VDE
Clearance and creepage
distance rating
Insulation strength
268
Tested in accor-
dance with
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-31
IEC 60068-2-32
EN 55011/A
EN 55022/B
EN 50081-1
(domestic area)
IEC 61000-4-2
Severity 3
IEC 61000-4-3
IEC 61000-4-6
IEC 61000-4-4
Severity 3
IEC 61000-4-5
Severity 3
IEC 60664,
IEC 61131-2,
EN 50178
cULus to UL 508,
CSA C22.2 No.
142
With LOGO!
230 R/RC,
also VDE 0631
IEC 61131-2
Values
IP20
5 ... 9 Hz (constant
amplitude 3.5 mm)
9 ... 150 Hz (constant
acceleration 1 g)
18 shocks
(half-sine wave
15g/11 ms)
Drop height 50 mm
1 m
Limit class B group 1
8 kV air discharge
6 kV contact discharge
Field strength 10 V/m
10 V
2 kV (supply and sig-
nal lines)
1 kV (power lines)
symmetrical
2 kV (power lines)
asymmetrical
Fulfilled
Fulfilled
LOGO! Manual