Siemens Logo! Manual page 162

Hide thumbs Also See for Logo!:
Table of Contents

Advertisement

LOGO! functions
Timing diagram
En
Q
T is
busy
Functional description
The 0 to 1 transition at input En triggers a random on-delay
time between 0 s and T
delay time has expired and if the signal at input En remains
hi at least for the duration of this time.
The time is reset if input En is reset before the on-delay
time has expired.
A 1 to 0 transition at input EN triggers a random on-delay
time between 0 s and T
The output is reset after the off-delay time has expired, pro-
vided input En remains lo at least for the duration of this
time.
The time is reset if the signal at input En changes to 1
again before the off-delay time has expired.
The time expired is reset after a power failure.
154
T
T
L
H
. The output is set when the on-
H
.
L
The bold section of
the timing diagram
also appears in the
symbol of the random
generator.
LOGO! Manual
A5E00380835-01