Viewing The Mi, Mn And Ot Values; Limit Value Of Ot - Siemens Logo! Manual

Hide thumbs Also See for Logo!:
Table of Contents

Advertisement

LOGO! functions

Viewing the MI, MN and OT values

S
LOGO! Basic with display unit: You can open the param-
eter assignment mode when the system is in RUN to
view the actual values of MI, MN and OT.
S
LOGO! Basic without display unit: In LOGO!Soft Com-
fort, you can use the Online Test to read these values
(for further information, see Chapter 7).

Limit value of OT

The value of the operating hours in OT are retained when
you reset the hours counter with a signal at input R. The
hours counter OT continues the count as long as En = 1,
irrespective of the status at the reset input R.
The counter limit of OT is 99999 h.
The hours counter stops when it reaches this value.
In programming mode, you can set the initial value of OT.
The counter starts operation at any value other than zero.
MN is automatically calculated at the START, based on the
MI and OT values
(Example: MI = 100, OT = 130, the result is MN = 70).
Preset of the Par parameter
View in programming mode:
B16
MI = 0100h
Q!0:R+En
OT =00000h
MI is the configurable time interval. Its permissible range of
values lies between 0 and 9999 hours.
176
+
or
Time ex-
pired
B16
MI = 0100h
Q!0:R
OT =00000h
LOGO! Manual
A5E00380835-01
+