Logo! Dm8 12/24R - Siemens Logo! Manual

Hide thumbs Also See for Logo!:
Table of Contents

Advertisement

Technical data
A.8 Technical data: LOGO! 12/24... and

LOGO! DM8 12/24R

Power supply
Input voltage
Permissible range
Reverse polarity protection
Power consumption
S
12 V DC
S
24 V DC
Voltage failure buffering
S
12 V DC
S
24 V DC
Power loss
S
12 V DC
S
24 V DC
Backup of the real-time clock
at 25 _C
Accuracy of the real-time
clock
Electrical isolation
Digital inputs
Number
Electrical isolation
Input voltage L+
S
Signal 0
g
S
Signal 1
288
LOGO! 12/24RC
LOGO! 12/24RCo
12/24 V DC
10.8 ... 28.8 V DC
Yes
30 ... 140 mA
20 ... 75 mA
typ. 2 ms
typ. 5 ms
0.3 ... 1.7 W
0.4 ... 1.8 W
typ. 80 h
typ. "2 s / day
No
8
No
< 5 V DC
> 8 V DC
LOGO! DM8
12/24R
12/24 V DC
10.8 ... 28.8 V DC
Yes
30 ... 140 mA
20 ... 75 mA
typ. 2 ms
typ. 5 ms
0.3 ... 1.7 W
0.4 ... 1.8 W
No
4
No
< 5 V DC
> 8 V DC
LOGO! Manual
A5E00380835-01