Short circuit-proof and over-
load-proof
Short-circuit current limitation
Derating
Short circuit-proof cos 1
Short-circuit proof cos 0.5 to
0.7
Parallel output circuit for
power increase
Protection of output relay (if
desired)
Switching rate
Mechanical
Electrical
Ohmic load/lamp load
Inductive load
(1): When LOGO! 24, LOGO! 24o or LOGO! DM8 24, LOGO! DM16 24 are
switched on, signal 1 is sent to the digital outputs for about 50 microseconds.
Take this into account, especially when using devices that react to short
pulses.
LOGO! Manual
A5E00380835-01
LOGO! DM8 24
Yes
Approx. 1 A
none; across the
entire temperature
range
Not permitted
10 Hz
10 Hz
0.5 Hz
Technical data
LOGO! DM16 24
Yes
Approx. 1 A
None; across the
entire temperature
range
Not permitted
10 Hz
10 Hz
0.5 Hz
281