4.1.12 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and over-current protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below
to protect service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case
of a short-circuit on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal
over-current protection that can be used for upstream overload protection (UL-applications excluded). See par. 4-18
circuit breakers can be used to provide the over-current protection in the installation. Over-current protection must always be carried out according to
national regulations.
Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
P110 - P250
P315 - P450
380-480 V, frame size D
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the
drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Bussmann
Bussmann
Size/
E1958
E4273
Type
JFHR2**
T/JDDZ**
P110
FWH-
JJS-
300
300
P132
FWH-
JJS-
350
350
P160
FWH-
JJS-
400
400
P200
FWH-
JJS-
500
500
P250
FWH-
JJS-
600
600
Table 4.1: Frame size D, Line fuses, 380-480 V
380 - 480 V
380 - 480 V
SIBA
LittelFuse
E180276
E71611
JFHR2
JFHR2**
2061032.315
L50S-300
2061032.35
L50S-350
2061032.40
L50S-400
2061032.50
L50S-500
2062032.63
L50S-600
MG.11.O1.02 - ADAP-KOOL
®
is a registered Danfoss trademark
Current Limit
type gG
type gR
Ferraz-
Bussmann
Bussmann
Shawmut
E4274
E125085
E60314
H/JDDZ**
JFHR2*
JFHR2**
A50-P300
NOS-
170M3017
300
A50-P350
NOS-
170M3018
350
A50-P400
NOS-
170M4012
400
A50-P500
NOS-
170M4014
500
A50-P600
NOS-
170M4016
600
4 Electrical Installation
4
. Moreover, fuses or
Internal
Option
Bussmann
170M3018
170M3018
170M4016
170M4016
170M4016