2.1.10 IT mains

IT mains
Do not connect frequency converters with RFI-filters to mains supplies with a voltage between phase and earth of more than 440 V
for 400 V converters and 760 V for 690 V converters.
For 400 V IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.
For 690 V IT mains and delta earth (grounded leg), mains voltage may exceed 760 V between phase and earth.
Par. 14-50
RFI Filter
can be used to disconnect the internal RFI capacitors from the RFI filter to ground.
2.1.11 Software Version and Approvals: ADAP-KOOL Drive AKD 102
This manual can be used with all ADAP-KOOL Drive AKD 102 frequency converters with software version 2.1.x.
The software version number can be seen from par. 15-43
2.1.12 Disposal instruction
ADAP-KOOL Drive AKD 102
Software version: 2.1.x
Software Version
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid leg-
islation.