5 How to Operate the Frequency Converter
Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for Graphical LCP (GLCP)
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s
4. The frequency converter is now programmed according to
5
default settings
64
My Personal Menu
.
This parameter initialises all except:
Par. 15-00
Par. 15-03
Par. 15-04
Par. 15-05
MG.11.O1.02 - ADAP-KOOL
®
is a registered Danfoss trademark
®
ADAP-KOOL
Drive AKD 102 High Power
Operating Hours
Power Up's
Over Temp's
Over Volt's
Need help?
Do you have a question about the ADAP-KOOL AKD 102 and is the answer not in the manual?